UMAX0608XX‐1000. Tri‐Axial J1939 CAN Inclinometer. Version 9B
Page: 49-66
Figure 31. CAN Output Message #3 Example Configuration
As the last step, if the default functionality is not required, the user can disable sending
SSI2
CAN messages in the
CAN Output Message #2
function block by setting the
Transmission
Enable
configuration parameter to
No
.
1
In firmware V1.xx for AX060800, AX060806, AX060807 the user will need to disable SSI CAN
messages in the CAN Output Message #1 function block.
The inclinometer configuration is finished. Now the unit operates according to the new user
requirements. The configuration parameters are all set and are already written to the non-
volatile unit memory. The users can save them to a setpoint file for future use, if necessary.
The setpoint file for this example is available upon request.
4.4.3 Configuring Analog Signal Outputs
Analog signal outputs of the AX0610000 inclinometer can be used to output any internal
inclinometer signals.
For example, let us output the tilt alarm signal described in 4.4.1 as a 5V discrete signal on the
analog signal output # 3. Let the signal be described as 0V – Alarm Off and 5V – Alarm On.
Other requirements stay the same.