Room Alert User’s Guide
45
WiSH Options
( Room Alert 32W)
Navigate to
Settings
Advanced
WiSH Options
to access advanced options and filters for
each Wireless Sensor Hub (WiSH) or Wireless Sensor Hub & Powered Relay (WiSPR).
Advanced WiSH Sensor Options
1.
In Enable WiSH Lost Communications Alarms, you may leave the box checked, which is
the default, or disable it by unchecking the box.
2.
In WiSH Timeout, you may enter the number of packets to allow Room Alert to miss
before an alarm is generated. You may enter a value between 10 and 254; the default is
10. This prevents false alerts if the wireless signal is temporarily interrupted.
3.
In WiSH Sensors Enabled, you may specify the maximum number of WiSH or WiSPR units
you want to monitor. You may leave the default, 10, or enter a lower number.
4.
Only click
Reset All WiSH Sensors
if you wish to clear settings for all of your WiSH
sensors and change them back to defaults.
WiSH Sensor Filter Configuration
In this section, you may block your Room Alert 32W from communicating with some or all of
your WiSH sensors. You may need this feature if you want only certain WiSHs recognized.
1.
In Enable WiSH Sensor Filter, check the box to enable filtering. It is disabled (unchecked)
by default.