Room Alert User’s Guide
General Alarm Configuration
Degrees Within Threshold Before Alarm Is Cleared
( Room Alert 32E/W)
You may use this feature, available in the Room Alert 32E/W, to adjust how close your digital
temperature sensor readings must get to a high or low threshold before their alarms clear. For
example, with the default setting here of 1º and a high threshold of 80º, your temperature
sensor will alarm when the temperature rises above 80º and clear when it falls below 79º;
likewise, with a low threshold of 60º, the sensor will alarm when the temperature falls below 60º
and clear when it rises above 61º.
1.
In Degrees Within Threshold Before Alarm Is Cleared, you may leave the default, 1, or
enter a value between 0.1 and 25.5.
2.
Select
Save Settings
at the top or bottom of the page. Your Room Alert will
automatically reboot and commit your changes.
Trigger Alarm If Sensor Is Disconnected?
You may configure your Room Alert to send an alert if any of the external digital sensors are
disconnected from the unit.
1.
Check
Trigger Alarm If Sensor Is Disconnected?
if you want to receive an alert if an
external digital sensor becomes disconnected. This check box is blank by default.
2.
Select
Save Settings
at the top or bottom of the page. Your Room Alert will
automatically reboot and commit your changes.