Entering this menu allows you access to the following four calibration functions via the keypad:
1.
-Lo-
Low (Zero) Calibration
2.
-Hi-
High (Span) Calibration
3.
-PID-
Proportional, Integral and Derivative Gain Adjustment
4.
-Snsr-
Sensor Calibration
5.
-Trnd-
Transducer Calibration
6.
-mA-
Milliampere Calibration
7.
-Xmr-
Transmitter Calibration
Menu 3: Cofg (Configuration)
Entering this menu allows you access to the following five configuration functions via the keypad:
1.
-Flow-
Positioner Output Flow Characteristics
2.
-Type-
Positioner Recognition of Magnetic Feedback, Rotary or Linear
3.
-Flop-
Positioner Fail Position, Open or Closed
4.
-OPSP-
Positioner Opening Speed Adjustment
5.
-CLSP-
Positioner Opening Speed Adjustment
6.
-EDb -
Positioner Operating Dead-band Adjustment
7.
-LCD-
LCD Menu Timeout Adjustment
These functions allow display, speed and valve characteristic changes from standard factory set-
tings.
Menu 4: Stro (Manual Override of Input Signal)
Entering this menu allows you access to the following three stroking functions via the
keypad:
1.
-Adjs-
Adjustment of Positioner to Any Position Using Keypad Arrows
2.
-OP-
Open, Sets the Valve to the Full Open Position
3.
-CLs-
Close, Sets the Valve to the Full Closed Position
These functions set the positioner to digital control mode (
input current independent
)
and therefore allow override of the control signal.
4.8 Description of Functions
LO
This function serves to set the fail position of the actuator/valve. Initially during
this calibration the valve is driven to the fail position (hard stop). The user will
notice full pressure to Outlet Port 2 and zero pressure to Outlet Port 1. After a
short period of time pressure will increase in Outlet Port 1 and the valve will be
driven to the fully energized position and then back to the fail position. At this
point the user has the option to select the hard stop as low (zero) position or to
select an arbitrary position as low (zero) position.
HI
This function serves to set the fully energized (full travel) position of the
actuator/valve. Initially during this calibration the valve is driven to the fully