4.4 Exiting Calibration
To exit calibration mode and return to normal operation use the
up arrow
key as follows:
If the positioner is at
Menu level
in the calibration, as determined by LCD displaying a
Menu name only (
MCAL
, etc.), press the
up arrow
key once to exit
CAL
mode.
If the positioner is at
function level
in the calibration, as determined by LCD displaying a
function and Menu name only (
MCAL Lo
, etc.), press the
up arrow
key once to enter the
Menu level and once more to exit
CAL
mode.
If the positioner is performing any calibration function (e.g.,
ACAL Trnd
), press up and
down key simultaneously to abort the current operation and go to the normal operation
screen.
When the calibration mode is exited the Menu and function names will no longer be dis-
played by the LCD. The LCD will be displayed “OK”.
4.5 Configure the Positioners Parameters
From the menu level press the down arrow button until the Cofg (Configuration Menu) is shown
on the display (Configuration Routine Shown Below). Enter this menu and change any of the
parameters, if other than the factory settings are needed. The factory settings are highlighted.