E1070 Service Manual
132
4 SensorComm Hardware Configuration and
Calibration
4.1
Introduction
SensorComm will only connect to communications port #1.
Main PCB jumper settings need to be set for RS485. This requires disassembly of the
indicator and moving the jumper on JMP1 to pins 2 and 3. See
for disassembly drawings and
for the JMP1 position.
Wiring connections, at the indicator, are shown in the table above.
Refer to SensorComm installation manual for SensorComm box wiring.
4.2
Enable SensorComm
1.
Access the Service (0701) menu…
CAL
is displayed.
2.
Press the
UNITS
key…
SCALE
is displayed.
3.
Press the
key…
SourCE
is displayed.
4.
Press the
key…
ANALOG
or
S-Com
is displayed.
5.
Press the
UNITS
key to display
S-Com
.
6.
Press the
ENTER
key…
SensorComm is now enabled.
7.
Press the
ESC
key to exit and
ENTER
to save the configuration at the prompt.
Com Port #1 RS232, RS485 or SensorComm
GND
TX / TXA
RTS/TXB
RX / RCA
CTS/RCB
+15VDC
BLK
RED
GRN
YLW
BLU
WHT
Only one SensorComm box can be connected to the indicator. The indicator can be
1000 feet from the SensorComm box.
Summary of Contents for E1070
Page 1: ...Model E1070 Indicator Service Manual NORTH AMERICA AWT35 500106 Issue AF March 2010 ...
Page 6: ...6 E1070 Service Manual ...
Page 51: ...E1070 Service Manual 51 3 4 Service Menu Table 3 1 Printalbe Characters Chart ...
Page 146: ...146 E1070 Service Manual 8 Network Connections ...
Page 150: ...150 E1070 Service Manual 10 2 Complete Service Menu ...
Page 153: ...E1070 Service Manual 153 11 3 Wall Mount Application ...
Page 154: ...154 E1070 Service Manual 11 4 System Block Diagram ...
Page 155: ...E1070 Service Manual 155 11 5 Keypad Schematic and Power Supply Bd P N 60071 0016 ...
Page 158: ...158 E1070 Service Manual 11 8 I O External Calbe Identification Pin outs ...
Page 162: ...162 E1070 Service Manual ...
Page 163: ......