2.3 EOL Zone Wiring
The AV-5009 factory default is 8 zones none EOL zones. If EOL mode is required move
jumpers as shown in figure 2.2. The zones are referred to –V.
If zone 4 or 8 selected as EOL type add in series with the 2.2.K (zone 4) or 4.7K (zone
8) resistor and the sensor contacts (relay. Refer to figure 2.3.
2.4 Keypad Wiring
Up to three AV-701 or AV-702 Keypads can be connected to AV-5009. When few
keypads are connected, wire each one directly to the panel, not from one keypad to the
other. Refer to drawing in next page.
When using few keypads connect them in parallel. Each keypad has four terminal wires:
(+) Power, connect to + Aux. Power
System Data, connect to OR
(
–
) Power, connect to
–
Aux. Power
System Strobe, connect to YE
F i g u r e 2 . 3 : W i r i n g m o r e t h e n o n e k e y p a d
Wire length for each Keypad should not exceed 100 meters (when using 0.5 mm2
wires).
For longer then 100 meters (320 feet) keypad wiring, contact manufacturer's consultant.
For AV-701/702TP (keypad with tamper) run five (5) wires. Connect the TMP terminal to
a 24H or Tamper zone.
Power at Keypad should be a minimum of 11.5 Volts.
IMPORTANT! Never run Keypad wires alongside telephone wires, high voltage
wires, or transmitting antennae. Wire the keypad wires separately and not in same
cable with other devices (telephone, PIR etc.)
For proper connection, refer to wiring diagrams at the end of the manual.