6. Other functions
86
© Copyright Reserved Autonics Co., Ltd.
i. -|Transparent setting guide|-
6.5
Auxiliary output (AUX 1/2)
The auxiliary output is an optional output for monitoring the status of the light curtain.
It is provided at the bottom of the emitter and receiver.
Do not use the auxiliary output for safety purposes. This output cannot be deactivated.
(1) Example of output mode
※
Example is based on the factory default.
•
AUX 1(receiver) - output mode: OSSD, output phase: Reverse
•
AUX 2(emitter) - output mode: Error/Lockout, output phase: Reverse
OSSD
Lockout condition
max. 50ms
※1
max. 50ms
※1
max. 50ms
※1
Auxiliary
output
1
Auxiliary
output
2
Error occurs
ON
OFF
ON
OFF
ON
OFF
※
1: It may differ depending on the series connection.
(2) Set auxiliary output mode
Select the output mode first and select the output phase. The output may differ depending on the output phase in the same
output mode. If the output phase is set to reverse, the output is switched to ON from OFF. If the output phase is normal, the
output is switched to OFF from ON.
The output mode and phase can be set via atLightCurtain. The SFLA (advanced type) supports atLightCurtain.
In case of the output mode of SFL (standard type), AUX 1 (receiver) is OSSD ON/OFF, and AUX 2 (emitter) is Error/Lockout.
No. Output mode
Description
Output phase
Reverse Normal
1
OSSD ON/OFF
The OSSD output is in the ON state.
OFF
ON
2
Error / Lockout
The light curtain is in the error or lockout condition.
3
Warning
The light curtain is in the warning condition.
4
Muting / Override
The muting or override function is activated.
5
Blanking
The blanking function is activated.
6
Blanking Error
All beams of fixed or floating blanking zone are not blocked.
7
External Test
The external test input is in the ON state.
8
Interlock
The interlock function is activated.
9
Reset-Hold
The light curtain is in the reset-hold wait time.
10
Light ON/OFF
All beams are clear and stable.
11
Sensitivity
Reduction
※1
The incident light level is less than the sensitivity reduction level.
※
1: Sensitivity reduction occurs when the current incident light level lasts for 30 minutes, with less than 15%
to 35% of the maximum incident light level.
For more information on the incident light level, see "4.3 Alarm for incident light level"
※
The OSSD output is switched to the OFF to prevent damage in the output circuit if the current over rated voltage
flows in the auxiliary output. The state maintains until the auxiliary ouput is switched depending on the sensing
or functional operation.