5. Safety-related function
68
© Copyright Reserved Autonics Co., Ltd.
i. -|Transparent setting guide|-
5.4.3 Change settings
You can change settings via setting switch or atLightCurtain.
Only SFLA (advanced type) support atLightCurtain to change settings.
Function
Item
Setting range
Factory default
Setting method
atLightCurtain
Setting switch
(pin no.)
Muting
Muting function
Enable/Disable
Disable
○
○(7)
Muting zone
※1
Detection zone
Entire zone
-
Muting mode
Standard mode/
Exit-only mode
Standard mode
Muting sequence
※2
One direction:
1→2/2→1
Both direction: 1↔2
1→2
Muting sensor 1
N.O./N.C.
N.O.
Muting sensor 2
N.O./N.C.
N.O.
Min value of mute input time limit
(T1min)
0.03-3.9sec
0.03sec
Max value of mute input time limit
(T1max)
0.1-10sec
3sec
Muting timeout (T2)
※3
0-3600sec
60sec
Exit-only muting wait time(T3)
0.1-4sec
4sec
※
When the function is activated by the setting switch, the setting range is the factory default.
※
1: Even if the beams set to the muting zone are blocked, the OSSD output remains ON state. When using a combination
of muting and blanking functions, the muting zone and the blanking zone can be overlapped.
The muting zone can be set manually or automatically in atLightCurtain.
For more information, see “
atLightCurtain User Manual.”
※
2: When muting mode is set to exit-only mode, the muting sequence cannot be set in both directions.
※
3: If you set the Muting timeout (T2) to 0, it is set to 'unlimited' and it may cause continuous muting condition
unintentionally. In this case, the operator should perform a sufficient risk assessment and take additional safety
measures.