3 Modbus Mapping Table
66
© Copyright Reserved Autonics Co., Ltd.
3.4.2.7
CH7-S4AI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400901 (0384)
03/06/16 R/W Alarm Set Copy
Copy alarm parameter Refer to channel table.
※
8
-
None
CH-1 to CH-12
400902 (0385)
03/06/16 R/W Alarm1 Type
Alarm 1 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
PV.Hi
400903 (0386)
03/06/16 R/W Alarm1 Ref CH
Alarm 1 reference
channel
Refer to channel table.
※
8
-
None
CH1toCH12
400904 (0387)
03/06/16 R/W Alarm1 Option
Alarm 1 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400905 (0388)
03/06/16 R/W Alarm1 Value
Alarm 1 set value
F.S. by each channel
Digit 1350.0
400906 (0389)
400907 (038A) 03/06/16 R/W Alarm1 Hysteresis Alarm 1 hysteresis
001 to 999
Digit 001
400908 (038B) 03/06/16 R/W Alarm1 ON Delay Alarm 1 output ON
delay time
0 to 3600
Sec. 0
400909 (038C) 03/06/16 R/W Alarm1 OFF Delay Alarm 1 output OFF
delay time
0 to 3600
Sec. 0
400910 (038D) 03/06/16 R/W Alarm1 Alarm No Alarm 1 output alarm
number
Refer to channel table.
※
8
-
None
400911 (038E) 03/06/16 R/W Alarm2 Type
Alarm 2 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
None
400912 (038F) 03/06/16 R/W Alarm2 Ref
Channel
Alarm 2 reference
channel
Refer to channel table.
※
8
-
None
400913 (0390)
03/06/16 R/W Alarm2 Option
Alarm 2 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400914 (0391)
03/06/16 R/W Alarm2 Value
Alarm 2 set value
F.S. by each channel
Digit 0
400915 (0392)
400916 (0393)
03/06/16 R/W Alarm2 Hysteresis Alarm 2 hysteresis
001 to 999
Digit 001
400917 (0394)
03/06/16 R/W Alarm2 ON Delay Alarm 2 output ON
delay time
0 to 3600
Sec. 0
400918 (0395)
03/06/16 R/W Alarm2 OFF Delay Alarm 2 output OFF
delay time
0 to 3600
Sec. 0
400919 (0396)
03/06/16 R/W Alarm2 Alarm No Alarm 2 output alarm
number
Refer to channel table.
※
8
-
None
400920 (0397)
03/06/16 R/W Alarm3 Type
Alarm 3 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
OFF
400921 (0398)
03/06/16 R/W Alarm3 Ref
Channel
Alarm 3 reference
channel
Refer to channel table.
※
8
-
None
400922 (0399)
03/06/16 R/W Alarm3 Option
Alarm 3 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400923 (039A) 03/06/16 R/W Alarm3 Value
Alarm 3 set value
F.S. by each channel
Digit 0
400924 (039B)
400925 (039C) 03/06/16 R/W Alarm3 Hysteresis Alarm 3 hysteresis
001 to 999
Digit 001
400926 (039D) 03/06/16 R/W Alarm3 ON Delay Alarm 3 output ON
delay time
0 to 3600
Sec. 0
400927 (039E) 03/06/16 R/W Alarm3 OFF Delay Alarm 3 output OFF
delay time
0 to 3600
Sec. 0
400928 (039F) 03/06/16 R/W Alarm3 Alarm No Alarm 3 output alarm
number
Refer to channel table.
※
8
-
None
400929 (03A0) 03/06/16 R/W Alarm4 Type
Alarm 4 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo,
5:SBA, 6:P.END
-
OFF
400930 (03A1) 03/06/16 R/W Alarm4 Ref
Channel
Alarm 4 reference
channel
Refer to channel table.
※
8
-
None
400931 (03A2) 03/06/16 R/W Alarm4 Option
Alarm 4 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400932 (03A3) 03/06/16 R/W Alarm4 Value
Alarm 4 set value
F.S. by each channel
Digit 0
400933 (03A4)
400934 (03A5) 03/06/16 R/W Alarm4 Hysteresis Alarm 4 hysteresis
001 to 999
Digit 001
400935 (03A6) 03/06/16 R/W Alarm4 ON Delay Alarm 4 output ON
delay time
0 to 3600
Sec. 0
400936 (03A7) 03/06/16 R/W Alarm4 OFF Delay Alarm 4 output OFF
delay time
0 to 3600
Sec. 0
400937 (03A8) 03/06/16 R/W Alarm4 Alarm No Alarm 4 output alarm
number
Refer to channel table.
※
8
-
None
400938 to
400950
03/06/16 R/W Reserved
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......