3
Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
59
3.4.2
ALARM SETUP(Alarm setting)
3.4.2.1
CH1-S1AI - 1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400601 (0258)
03/06/16 R/W Alarm Set Copy
Copy alarm
parameter
Refer to channel table.
※
8
-
None
CH-1 to CH-12
400602 (0259)
03/06/16 R/W Alarm1 Type
Alarm 1 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
PV.Hi
400603 (025A) 03/06/16 R/W Alarm1 Ref CH
Alarm 1 reference
channel
Refer to channel table.
※
8
-
None
CH-1 to CH-12
400604 (025B) 03/06/16 R/W Alarm1 Option
Alarm 1 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400605 (025C) 03/06/16 R/W Alarm1 Value
Alarm 1 set value
F.S. by each channel
Digit 1350.0 Signed short
400606 (025D)
400607 (025E) 03/06/16 R/W Alarm1 Hysteresis
Alarm 1 hysteresis 001 to 999
Digit 001
400608 (025F) 03/06/16 R/W Alarm1 ON Delay
Alarm 1 output ON
delay time
0 to 3600
Sec. 0
400609 (0260)
03/06/16 R/W Alarm1 OFF Delay Alarm 1 output OFF
delay time
0 to 3600
Sec. 0
400610 (0261)
03/06/16 R/W Alarm1 Alarm No
Alarm 1 output alarm
number
Refer to channel table.
※
8
-
None
400611 (0262)
03/06/16 R/W Alarm2 Type
Alarm 2 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
None
400612 (0263)
03/06/16 R/W Alarm2 Ref Channel Alarm 2 reference
channel
Refer to channel table.
※
8
-
None
400613 (0264)
03/06/16 R/W Alarm2 Option
Alarm 2 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400614 (0265)
03/06/16 R/W Alarm2 Value
Alarm 2 set value
F.S. by each channel
Digit 0
400615 (0266)
400616 (0267)
03/06/16 R/W Alarm2 Hysteresis
Alarm 2 hysteresis 001 to 999
Digit 001
400617 (0268)
03/06/16 R/W Alarm2 ON Delay
Alarm 2 output ON
delay time
0 to 3600
Sec. 0
400618 (0269)
03/06/16 R/W Alarm2 OFF Delay Alarm 2 output OFF
delay time
0 to 3600
Sec. 0
400619 (026A) 03/06/16 R/W Alarm2 Alarm No
Alarm 2 output alarm
number
Refer to channel table.
※
8
-
None
400620 (026B) 03/06/16 R/W Alarm3 Type
Alarm 3 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
OFF
400621 (026C) 03/06/16 R/W Alarm3 Ref Channel Alarm 3 reference
channel
Refer to channel table.
※
8
-
None
400622 (026D) 03/06/16 R/W Alarm3 Option
Alarm 3 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400623 (026E) 03/06/16 R/W Alarm3 Value
Alarm 3 set value
F.S. by each channel
Digit 0
400624 (026F)
400625 (0270)
03/06/16 R/W Alarm3 Hysteresis
Alarm 3 hysteresis 001 to 999
Digit 001
400626 (0271)
03/06/16 R/W Alarm3 ON Delay
Alarm 3 output ON
delay time
0 to 3600
Sec. 0
400627 (0272)
03/06/16 R/W Alarm3 OFF Delay Alarm 3 output OFF
delay time
0 to 3600
Sec. 0
400628 (0273)
03/06/16 R/W Alarm3 Alarm No
Alarm 3 output alarm
number
Refer to channel table.
※
8
-
None
400629 (0274)
03/06/16 R/W Alarm4 Type
Alarm 4 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
OFF
400630 (0275)
03/06/16 R/W Alarm4 Ref Channel Alarm 4 reference
channel
Refer to channel table.
※
8
-
None
400631 (0276)
03/06/16 R/W Alarm4 Option
Alarm 4 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400632 (0277)
03/06/16 R/W Alarm4 Value
Alarm 4 set value
F.S. by each channel
Digit 0
400633 (0278)
400634 (0279)
03/06/16 R/W Alarm4 Hysteresis
Alarm 4 hysteresis 001 to 999
Digit 001
400635 (027A) 03/06/16 R/W Alarm4 ON Delay
Alarm 4 output ON
delay time
0 to 3600
Sec. 0
400636 (027B) 03/06/16 R/W Alarm4 OFF Delay Alarm 4 output OFF
delay time
0 to 3600
Sec. 0
400637 (027C) 03/06/16 R/W Alarm4 Alarm No
Alarm 4 output alarm
number
Refer to channel table.
※
8
-
None
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......