3 Modbus Mapping Table
62
© Copyright Reserved Autonics Co., Ltd.
3.4.2.3
CH3-S2AI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400701 (02BC) 03/06/16 R/W Alarm Set Copy
Copy alarm
parameter
Refer to channel table.
※
8
-
None
CH-1 to CH-12
400702 (02BD) 03/06/16 R/W Alarm1 Type
Alarm 1 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
PV.Hi
400703 (02BE) 03/06/16 R/W Alarm1 Ref CH
Alarm 1 reference
channel
Refer to channel table.
※
8
-
None
CH-1 to CH-12
400704 (02BF) 03/06/16 R/W Alarm1 Option
Alarm 1 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400705 (02C0) 03/06/16 R/W Alarm1 Value
Alarm 1 set value
F.S. by each channel
Digit 1350.0
400706 (02C1)
400707 (02C2) 03/06/16 R/W Alarm1 Hysteresis Alarm 1 hysteresis 001 to 999
Digit 001
400708 (02C3) 03/06/16 R/W Alarm1 ON Delay
Alarm 1 output ON
delay time
0 to 3600
Sec. 0
400709 (02C4) 03/06/16 R/W Alarm1 OFF Delay Alarm 1 output OFF
delay time
0 to 3600
Sec. 0
400710 (02C5) 03/06/16 R/W Alarm1 Alarm No
Alarm 1 output alarm
number
Refer to channel table.
※
8
-
None
400711 (02C6) 03/06/16 R/W Alarm2 Type
Alarm 2 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
None
400712 (02C7) 03/06/16 R/W Alarm2 Ref Channel Alarm 2 reference
channel
Refer to channel table.
※
8
-
None
400713 (02C8) 03/06/16 R/W Alarm2 Option
Alarm 2 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400714 (02C9) 03/06/16 R/W Alarm2 Value
Alarm 2 set value
F.S. by each channel
Digit 0
400715 (02CA)
400716 (02CB) 03/06/16 R/W Alarm2 Hysteresis Alarm 2 hysteresis 001 to 999
Digit 001
400717 (02CC) 03/06/16 R/W Alarm2 ON Delay
Alarm 2 output ON
delay time
0 to 3600
Sec. 0
400718 (02CD) 03/06/16 R/W Alarm2 OFF Delay Alarm 2 output OFF
delay time
0 to 3600
Sec. 0
400719 (02CE) 03/06/16 R/W Alarm2 Alarm No
Alarm 2 output alarm
number
Refer to channel table.
※
8
-
None
400720 (02CF) 03/06/16 R/W Alarm3 Type
Alarm 3 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
OFF
400721 (02D0) 03/06/16 R/W Alarm3 Ref Channel Alarm 3 reference
channel
Refer to channel table.
※
8
-
None
400722 (02D1) 03/06/16 R/W Alarm3 Option
Alarm 3 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400723 (02D2) 03/06/16 R/W Alarm3 Value
Alarm 3 set value
F.S. by each channel
Digit 0
400724 (02D3)
400725 (02D4) 03/06/16 R/W Alarm3 Hysteresis Alarm 3 hysteresis 001 to 999
Digit 001
400726 (02D5) 03/06/16 R/W Alarm3 ON Delay
Alarm 3 output ON
delay time
0 to 3600
Sec. 0
400727 (02D6) 03/06/16 R/W Alarm3 OFF Delay Alarm 3 output OFF
delay time
0 to 3600
Sec. 0
400728 (02D7) 03/06/16 R/W Alarm3 Alarm No
Alarm 3 output alarm
number
Refer to channel table.
※
8
-
None
400729 (02D8) 03/06/16 R/W Alarm4 Type
Alarm 4 operation
mode
0:OFF, 1:PV.Hi, 2:PV.Lo,
3:DV.Hi, 4:DV.Lo, 5:SBA,
6:P.END
-
OFF
400730 (02D9) 03/06/16 R/W Alarm4 Ref Channel Alarm 4 reference
channel
Refer to channel table.
※
8
-
None
400731 (02DA) 03/06/16 R/W Alarm4 Option
Alarm 4 option
0:None, 1:Latch, 2:StBy,
3:La+St
-
None
400732 (02DB) 03/06/16 R/W Alarm4 Value
Alarm 4 set value
F.S. by each channel
Digit 0
400733 (02DC)
400734 (02DD) 03/06/16 R/W Alarm4 Hysteresis Alarm 4 hysteresis 001 to 999
Digit 001
400735 (02DE) 03/06/16 R/W Alarm4 ON Delay
Alarm 4 output ON
delay time
0 to 3600
Sec. 0
400736 (02DF) 03/06/16 R/W Alarm4 OFF Delay Alarm 4 output OFF
delay time
0 to 3600
Sec. 0
400737 (02E0) 03/06/16 R/W Alarm4 Alarm No
Alarm 4 output alarm
number
Refer to channel table.
※
8
-
None
400738 to
400750
03/06/16 R/W Reserved
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......