1 Modbus RTU protocol
12
© Copyright Reserved Autonics Co., Ltd.
1.2
Read Input Status(Func02–02H)
Reads the input (1X reference) ON/OFF status in the Slave device.
(1)
Query(Master)
Slave Address
Function
(Command)
Starting Address
No. of Points(Number of data)
Error Check(CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response(Slave)
Slave Address
Function
(Command)
Byte Count
(Number of
data byte)
Data
Data
Data
Error Check(CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
The below example is to read the input status (ON: 1, OFF: 0) of 10EA within 10001(0000 H) to
10010(0009 H) on the Slave(Address 17) from the Master.
Query(Master)
Slave Address
Function
(Command)
Starting Address
No. of Points(Number of data)
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
02 H
00 H
00 H
00 H
0A H
## H
## H
The below example is when 10008(0007 H) to 10001(0000 H) value on the Slave is “ON-ON-
OFF-OFF-ON-ON-OFF-ON” and 10010(0009 H) to 10009(0008 H) value is “OFF-ON”.
Response(Slave)
Slave Address
Function
(Command)
Byte Count
(Number of
data byte)
Data
(00008 to 00001)
Data
(00010 to 00009)
Error Check(CRC16)
Low
High
11 H
02 H
02 H
CD H
01 H
## H
## H
CRC16
CRC16
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......