3
Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
55
3.4.1.11
CH11-S6UI-1
No(Address)
Func
R/W Parameter
Description
Set range
Unit Default Note
400501 (01F4) 03/06/16 R/W CH11 Input Set
Copy
CH11 copy input
parameter
Refer to channel
table.
※
4
-
None
400502 (01F5) 03/06/16 R/W CH11 Pen
Record
CH11 display and record
measuring value
0:OFF, 1:ON
-
ON
400503 (01F6) 03/06/16 R/W CH11 Pen Color CH11 record color
0:Violet, 1:Red,
2:Gray, 3:Green,
4:Blue, 5:Brown
-
Automati
c
set(CH1
to CH6)
(CH7 to
CH12)
Specify color.
400504 (01F7) 03/06/16 R/W CH11 Record
Zone
CH11 record zone
0:None, Zone1 to
Zone n
-
Zone(1
to N)
400505 (01F8)
03/06/16 R/W CH11 Tag Name CH11 channel name
1 to 6 characters
-
"CH-
□□"
400506 (01F9)
400507 (01FA)
400508 (01FB) 03/06/16 R/W CH11 Input Type CH11 input specification
Refer to input type
table.
※
5
-
TC-K
400509 (01FC) 03/06/16 R/W
CH11
Range/Scale
Point
CH11 decimal point
0:0, 1:0.0, 2:0.00,
3:0.000, 4:0.0000
-
Range
which
has
decimal
point
- TC/RTD type:
only available
0, 0.0
- Analog type:
Supports all. But
for Two Unit,
available 0:0,
1:0.0, 2:0.00
400510 (01FD) 03/06/16 R/W
CH11
Temp/Display
Unit
CH11 temperature unit (30209) Refer to
address.
-
℃
- TC/RTD type:
0:
℃
, 1:
℉
, 2:
˚K
-Analog type:
Supports all.
400511 (01FE) 03/06/16 R/W
CH11 Low
Range/Low
Graph Scale
※
7
CH11 lower limit input
value /CH11 lower limit
graph scale value
Min. value of sensor
input range to upper
limit input value/ Upper
limit graph scale value
- F.S 5%
-
-200
Refer to range
decimal point set
table.
※
6
400512 (01FF) 03/06/16 R/W
CH11 High
Range/High
Graph Scale
※
7
CH11 upper limit input
value /CH11 higher limit
graph scale value
Lower limit input value/
lower limit graph scale
value + F.S 5%) to
Max. sensor input
range
-
1350.0
400513 (0200)
03/06/16 R/W CH11 Low Scale CH11 analog lower limit
scale value
-99999 to 99999
Digit 0.0
Applied
depending on
the number of
decimal point of
CH11
Range/Scale
Point.
Ex) When scale
pointer value is
0.0, if inputting
9999, it is
recognized as
999.9
400514 (0201)
400515 (0202)
03/06/16 R/W CH11 High Scale CH11 analog upper limit
scale value
-99999 to 99999
Digit 100.0
400516 (0203)
400517 (0204)
03/06/16 R/W CH11 Special
Function
CH11 special function
TC/RTD input: 0:None,
1:Difference
Analog input: 0:Linear,
1:Root, 2:Square,
3:Two Unit
-
None
400518 (0205)
03/06/16 R/W Two Unit
Two Unit conversion
value
1 to 35
Digit 3
If 100 is set, it is
recognized as
1.00.
400519 (0206)
03/06/16 R/W CH11 Ref
Channel
CH11 reference channel
Refer to channel
table.
※
4
-
None
400520 (0207)
03/06/16 R/W CH11 Input Bias CH11 error correction
-9999 to 9999
Digit 0000
Uses correction
value which
applies scale
decimal point.
400521 (0208)
03/06/16 R/W CH11 Span
CH11 gradient
adjustment
0.100 to 5.000
Multipl
e
1.000
If 1000 is set, it
is recognized as
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......