1 Modbus RTU protocol
14
© Copyright Reserved Autonics Co., Ltd.
1.4
Read Input Registers(Func04–04H)
Reads the binary data of Input Registers(3X reference) in the Slave device.
(1)
Query(Master)
Slave Address
Function
(Command)
Starting Address
No. of Points(Number of data) Error Check(CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response(Slave)
Slave Address
Function
(Command)
Byte Count
(Number of
data byte)
Data
Data
Data
Error Check(CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
The below is to read 2EA value within Input Register 30001(0000 H) to 30002(0001 H) on the
Slave(Address 17) from the Master.
Query(Master)
Slave Address
Function
(Command)
Starting Address
No. of Points(Number of data)
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
04 H
00 H
00 H
00 H
02 H
## H
## H
The below example is when 30001(0000 H) value on the Slave is “10(A H)” and 30002(0001 H)
value is “20(14 H)”.
Response(Slave)
Slave Address
Function
(Command)
Byte Count
(Number of
data byte)
Data
Data
Error Check
(
CRC16)
High
Low
High
Low
Low
High
11 H
04 H
04 H
00 H
0A H
00 H
14 H
## H
## H
CRC16
CRC16
Summary of Contents for krn100 series
Page 1: ...Preface Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 18: ...1 Modbus RTU protocol 18 Copyright Reserved Autonics Co Ltd ...
Page 82: ......