2 Modbus TCP protocol
22
© Copyright Reserved Autonics Co., Ltd.
2.3
Read Holding Registers(Func03–03H)
Reads the binary data of Holding Registers(4X reference) in the Slave device.
(1)
Query(Master)
MBAP Header
Function
(Command)
Starting Address
No. of Points(Number of data
)
High
Low
High
Low
7Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response(Slave)
MBAP Header
Function
(Command)
Byte Count
(Number of data
byte)
Data
Data
Data
High
Low
High
Low
High
Low
7Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
The below example is to read 2EA value within Holding Register 400001(0000 H) to
400002(0001 H) on the Slave from the Master.
Query(Master)
MBAP Header
Function
(Command)
Starting Address
No. of Points(Number of data)
High
Low
High
Low
00 0a 00 00 00 06 01H
03 H
00 H
00 H
00 H
02 H
The below example is when 400001(0000 H) value on the Slave is “555(22B H)” and
400002(0001 H) value is “100 (64 H)”.
Response(Slave)
MBAP Header
Function
(Command)
Byte Count
(Number of data
byte)
Data
Data
High
Low
High
Low
00 0a 00 00 00 07 01H 03 H
04 H
02 H
2B H
00 H
64 H