Chapter 8: Installation and Wiring
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Do-more T1H Series PLC User Manual, 1st Edition, Rev. C
8-22
External 24VDC Wiring Options
DC output and analog I/O modules do not have direct access to the internally bussed 24VDC.
External user supplied 24VDC power, or auxiliary 24VDC from the T1K-01AC, can be
applied directly to one end of the DC I/O module base terminal (V and COM) rows and
jumpered across each base as needed in a system. This creates a “bus” (row) of 24VDC and a
bus of 0VDC power. Be sure not to exceed the supply’s power budget.
Using T1K-01AC for External 24VDC Power
Using an External 24VDC Power Supply
USB
PGM
PORT
RUN
I/O
ERR
USB
TX
RX
TERM
RUN
STOP
T1H-DM1E
USB
PGM
PORT
RUN
I/O
ERR
USB
TX
RX
TERM
RUN
STOP
T1H-DM1E
Use T1K-01AC external 24VDC to
create a power bus for DC modules.
Place wire jumpers from one DC I/O module
base to another as necessary to continue
the external 24VDC power bus.
Use an external 24VDC power supply to
create a power bus for the DC modules.
Place wire jumpers from one DC I/O module
base to another as necessary to continue
the external 24VDC power bus.
WARNING: The T1H Series PLC does not support any Hot-Swap features.