Chapter 8: Installation and Wiring
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Do-more T1H Series PLC User Manual, 1st Edition, Rev. C
8-14
Example Using T1K-05CBL-RR-1 and T1K-05CBL-LL Expansion Cables
USB
PGM
PORT
RUN
I/O
STAT
USB
TX
RX
TERM
RUN
STOP
T1H-DM1E
Power Supply #1
(a power supply must be
the left most component
in a system followed by
the CPU)
I/O Addressing
I/O Addressing
I/O Addressing
Power Supply #2
1st Local Expansion I/O
2nd Local Expansion I/O
Local Base I/O
T1K-05CBL-RR-1
Power Supply #3
T1K-05CBL-LL
CPU
Do not connect a
T1K-05CBL-LL to the
left side of the local
I/O base.
A power supply cannot
be used on a base that is
connected to a system by
a T1K-05CBL-RR-1.
System shown above:
The first power supply powers the CPU and the two I/O modules to
its right. The second power supply powers the two modules to its right and the three I/O
modules on the first local expansion base. When a T1K-05CBL-RR-1 is used, the expansion
I/O assignments are from right to left (reversed). A power supply cannot be used on a base
that is connected to a system by a T1K-05CBL-RR-1. Power Supply #3 powers the three
I/O modules to its right on the second local expansion base. This is only an example and the
power budget requirements vary depending on the I/O modules used.