Assembly Instructions
•
Spindle Drive SP -24 V / 230 V
9000002601.doc
Page
31
of
34
Maintenance and Service / Cleaning
In order to ensure troublefree operation the following opera-
tions shall be carried out every 1000 opening cycles, however
at least once
a year according to DIN18232 / VdS- guidelines
Model Building Regulations and individual manufacturer’s
guidelines.
1. Disconnect the system from the mains power supply when
cleaning or carrying out other maintenance work.
2. Check all mountings and clamping screws for tight fit and
re-tighten, if necessary.
3. Check the system for imbalance and signs of wear or
damage to cables /springs and fittings.
4. Check for optimal positioning of the casements in the
window frame. Adjust alignment of window fittings and, if
necessary, seal pressure depth.
5. Do not repair the drive yourself if defective. Do not attempt
to remove the drive housing or accessories.
Please consult the manufacturer if the device is damaged.
Only use original spare parts from the manufacturer.
6. When cleaning the window make sure that the drives do
not come directly into contact with water or detergents such
as alkaline or acid solutions.
7. Protect the drives from dirt and dust during the construction
phase or during internal and external renovation work
(e.g. wallpapering, painting, etc.).
Recommendation
To ensure that the system
works perfectly throughout
its long service life we
recommend having the
system serviced as
specified at least once
a year by our trained
specialist personnel.
Carry out regular functional
tests on a monthly basis.
Check the direction of travel
of the drives by operating
a manual OPEN-CLOSE
control switch.
ON
OFF
such as spindle,
chain, rack and pinion
Drive
Manual controller
e.g. key switch
with OFF default setting
mi
n. 1,5m
Mount all manual controllers out
of reach for unauthorized persons
Instructions
OPEN
CLOSE
Sign
such as spindle, chain,
rack and pinion
Drive
Target group
This operating instructions is intended for operators
instructed in Natural Smoke Exhaust system (NSE / SHEV)
and natural ventilation of the window with knowledge of
operating modes, as well as the Rest-Risks of the system.
This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabili-
ties, or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not
play with the appliance.
Operation of power-operated windows
The manual switch with OFF default setting (e.g. key switch)
must be positioned within eyeshot of the operated window
but in a safe distance from moving parts.
If it is not a key switch, the operating element must be
mounted at a height of at least 1.5 m and out of reach for
unauthorized operation.
Drives
that are operated by a handheld controller must be
provided with a sign indicating how to use it. The sign shall
be fixed permanently and clearly visible.
During the opening operation of
power-operated windows all persons should be kept clear
off the window (directly below or right next to it, within the
opening radius of the casement) since operating the hand-
held controller may lead to uncontrolled movements of the
driven part, for example due to mechanical failure or
imbalance.
Do not allow children playing with fixed regulating and
control devices and keep remote controllers out of children’s
reach.
Keep all other persons away when operating a
switch with
OFF default setting
.
Do not operate the window
during repairs or maintenance work.
Operating Instructions
Maintenance and Service / Cleaning
21