49
Part-turn actuators SG 03.3 – SG 04.3
Operation instructions
with AUMATIC AC 01.1
1) Only for actuators with Profibus DP
Menu
Abbreviationindisplay Note
D3
INTERNAL WARNING
NO INTERNAL WARNING
No internal warnings have occurred
EEPROM FAILURE
EEprom of the logic defective. Help: Check logic, if necessary exchange EE-
prom
NO FACTORY PARAMS
No valid factory settings are available
D4
CONFIGURATION FAULTY
NO FAULT
AUMATIC is not configured incorrectly
END POSITION INPUTS
Setting of the
LIMIT/TORQUE SWITCH
(see M4104) does not correspond to
the configuration
ENDPOS. INPUTS
(see D0).
NO SWITCHING OFF
Setting of the
LIMIT/TORQUE SWITCH
(see M4104) does not correspond to
the configuration
CONTR. UNIT ACTUATOR
(see M4109).
D5
LOGIC HRDWR. VER.
Display of hardware version of logic
D6
LOGIC SFTWR.VER.
Display of software version of logic
D7
POT. VALUE
If a potentiometer is installed, the potentiometer’s voltage values are display-
ed here:
in line 2 the value in end position CLOSED,
in line 3 the current value and
in line 4 the value in end position OPEN
D8
RWG VALUE
If an RWG is installed, the RWG’s current values are displayed here:
in line 2 the value in end position CLOSED,
in line 3 the current value and
in line 4 the value in end position OPEN
DC
DP1 HRDWR. VER.
1)
Hardware version of the Profibus DP interface
DD
DP1 SFTWR. VER.
1)
Software version of the Profibus DP interface
DE
DP1 BUS STATUS
1)
BAUD SEARCH
The Profibus DP interface searches a baudrate
BAUD CONTROL
The found baudrate is monitored. Hereby the DP watchdog in the master is not
activated.
DP MODE
DP communication monitored, the DP watchdog in the master is activated
WAIT PRM
The Profibus DP interface waits for correct parameter data
WAIT CFG
The Profibus DP interface waits for correct configuration data
DATA EX
The Profibus DP interface is currently exchanging data with the master.
DP FAULT
The internal status machine has detected a fault
GC CLEAR
The Profibus DP interface has received a Global Control “CLEAR” telegram.
In this state the actuator can not be operated from REMOTE.
DATA WITH LENGTH 0
The Profibus DP interface receives data with length 0 (FailSafe telegrams)
CHANNEL 2 ACTIVE
The Profibus DP interface communicates via the second channel