12. Test run
12.1 Check whether type of seating is set correctly
(see page 55, subclause 16.9)
Switching off in the end positions must be by limit seating.
The type of seating can be set separately for direction CLOSE and
direction OPEN.
.
Set selector switch to position OFF (0), figure G1.
.
Select status indication
S0
:
Press push button
briefly, if necessary several times.
Push x times briefly
until
S0
appears
Check if end positions of the limit switching are set correctly:
.
Engage manual operation as described under clause 6.2 on page 8.
.
Move actuator manually to the respective end position.
End position CLOSED reached: LED yellow: illuminated
Indication in display:
CLOSED POSITION
End position OPEN reached:
LED green: illuminated
Indication in display:
OPEN POSITION
The LED signals described here are standard settings. Deviating from this,
individual LED's can also signal another information (see page 18)
.
If the end positions are not set correctly, the limit switching must be set
anew, as described on page 13.
When end positions are set correctly, perform a test run in motor operation,
as described below.
.
Set selector switch (figure G3) to position
LOCAL
(
I
).
.
Operate actuator with push buttons
OPEN
- STOP - CLOSE
.
Actuator runs in direction CLOSE: LED yellow: blinking
Indication in display:
RUNNING CLOSE
End position CLOSED reached: LED yellow: illuminated
Indication in display:
CLOSED POSITION
Actuator runs in direction OPEN: LED green: blinking
Indication in display:
RUNNING OPEN
End position OPEN reached:
LED green: illuminated
Indication in display:
OPEN POSITION
15
Part-turn actuators SG 03.3 – SG 04.3
Operation instructions
with AUMATIC AC 01.1
C
Figure G1
CLOSED (yellow) OPEN (green)
OFF
Figure G2
Figure G3