15. Indication, operation and setting of the AUMATIC
The setting of the AUMATIC is done with the push buttons of the local
controls (figure Q1).
15.1 Change settings
To change the settings, the following steps are required:
1) Set selector switch (figure Q1) to position OFF.
2) Press push button
and hold it for approx. 2 seconds until the group
M0
appears (see also page 21).
3) Make selection: e.g. M0 "
LANGUAGE/CONTRAST"
and confirm selection
with
.
15.2 Password protection
The settings of the AUMATIC are password-protected. In the factory, the
following password is set: 0000. If necessary, the password can be changed
(enter password: page 22; change password: page 36).
15.3 Factory setting
During the function test the AUMATIC is set according to the customer's
requirements and its details (comm. no., date of final test....) are stored in
the EEPROM (non-volatile memory) as factory settings. The AUMATIC can
always be reset to these factory settings (see "
FACTORY SETTING
",
page 47).
15.4 Control and display elements
15.4.1 The local controls
The push buttons on the local controls (figure Q1) have two functions,
depending on the selector switch position:
.
Selector switch in
position LOCAL
:
Run commands OPEN - STOP - CLOSE and Reset
.
Selector switch in
position OFF
:
Indication and change of parameters,
indication of status and diagnosis information
.
Selector switch in
position REMOTE
:
Indication of parameters,
indication of status and diagnosis information
15.4.2 LED indications
Five local LEDs (figure Q2) indicate different signals (see page 28,
Parameter
LED1
to
LED 5 LOCAL CONTROLS.
).
18
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
C
Selector switch:
LOCAL-OFF-REMOTE
Push-buttons:
Function for
Function
selector switch
for selector switch
in position LOCAL: in position OFF and REMOTE:
OPEN
scroll/ change values
STOP
scroll/ change values
CLOSE
confirm selection
Reset
C
Escape
Figure Q1: Local controls
LED V1
(yellow)
is illuminated
Actuator is in end position CLOSED
is blinking
Actuator runs in direction CLOSE (can be swit-
ched on or off via parameter “
BLINKER
” page 28)
LED V2
(red)
is illuminated
Torque fault CLOSED
1)
(max. set torque was ex-
ceeded before reaching the end position)
LED V3
(red)
is illuminated
Motor protection tripped
LED V4
(red)
is illuminated
Torque fault OPEN
1) (
max. set torque was excee-
ded before reaching the end position)
LED V5
(green)
is illuminated
Actuator is in end position OPEN
is blinking
Actuator runs in direction OPEN (can be switched
on or off via parameter “
BLINKER
” page 28)
1) not available
Figure Q2