Part-turn actuators SG 03.3 – SG 04.3
Operation instructions
with AUMATIC AC 01.1
1) Only for actuators with Profibus DP 2) Only for actuators with Modbus
Subgroup
Parameter
name
Sub-
menu
Standard
value
Min/M
ax
Valuetext
Note
M1F
MODBUS 1
2)
REDUNDANCY
M1FX5
2
ON,TX: BOTH
CHANNELS
CHANNEL CHECK
TIME
M1FX6
5,0
0.0
Modbus 1: Channel check time
(in s)
25,5
T-OFF
PROC.IMG.OUT
M1F07
0.3
0,1
Modbus 1: Dead time process
representation output (in ms)
25,5
SIZE OF
PROC.IMG.OUT
M1F08
6
0
Modbus 1: Length of the process
representation output
64
SIZE OF
PROC.IMG.IN
M1F09
18
0
Modbus 1: Length of the process
representation input
64
M1G
MODBUS 2
2)
BAUD RATE
M1GX1
5
0
300 BAUD
Modbus 2: Baud rate selection
1
600 BAUD
2
1200 BAUD
3
2400 BAUD
4
4800 BAUD
5
9600 BAUD
6
19200 BAUD
7
38400 BAUD
PARITY
M1GX2
1
0
NO, 2 STOP-
BITS
Modbus 2: Parity selection
1
EVEN, 1 STOP-
BIT
2
ODD, 1 STOP-
BIT
CONNECT-
CONTROL TIME
M1G03
3.0
0.1
Modbus 2: connection control
time (in s)
25.5
SLAVE ADDRESS M1GX4
247
1
Modbus 2: Slave address
247
REDUNDANCY
M1GX5
0
0
OFF
Modbus 2: Redundancy behav-
iour
1
ON,TX:ACTIVE
CHANNEL
2
ON,TX: BOTH
CHANNELS
CHANNEL CHECK
TIME
M1GX6
5.0
0.0
Modbus 2: Channel check time
(in s)
25.5
T-OFF
PROC.IMG.OUT
M1G07
0.3
1
Modbus 2: Dead time process
representation output (in ms)
255
SIZE OF
PROC.IMG.OUT
M1G08
6
0
Modbus 2: Length of the process
representation output
64
SIZE OF
PROC.IMG.IN
M1G09
18
0
Modbus 2: Length of the process
representation input
64