30
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
Subgroup
Parameter
name
Sub-
menu
Standard
value
Min/M
ax
Valuetext
Note
M14
I/O 1
ALARM CONTACT M14X1
2
0
FAULT GROUP 1
Fault + Not ready
1
FAULT GROUP 2
not available
2
FAULT GROUP 3
Fault
3
FAULT GROUP 4
not available
4
FAULT GROUP 5
Fault + Not ready + Warning
5
FAULT GROUP 6
Fault + Not ready without thermo
fault
6
FAULT GROUP 7
not available
7
FAULT GROUP 8
Fault without thermal fault
8
FAULT GROUP 9
not available
9
FAULT GROUP 10
Fault + Not ready + Warnings
without thermal fault
OUTPUT
CONTACT 1
M14X2
2
0
NOT USED
Relay is not operated
1
CLOSED POSI-
TION
Signal LSC (WSR)
2
OPEN
POSITION
Signal LSO (WOEL)
3
RUNNING CLOSE
Actuator runs CLOSE
4
RUNNING OPEN
Actuator runs OPEN
5
ACTUATOR
MOVING
Actuator is running from LOCAL,
REMOTE or in manual operation
(without position transmitter only
the LOCAL or REMOTE operati-
on is indicated).
6
LSC (WSR)
Limit switch CLOSE operated
7
LSO (WOEL)
Limit switch OPEN operated
8
TSC (DSR)
not available
9
TSO (DOEL)
not available
10
THERMAL
FAULT
Motor protection has tripped
(reset may be necessary)
11
TORQUE FAULT
(CLOSE)
not available
12
TORQUE FAULT
(OPEN)
not available
13
TORQUE FAULT
(GEN.)
not available
14
SETPOINT E1
LOSS
Nominal value signal is by 0.3 mA
lower than the lowest value pro-
grammed
15
FEEDBACK E2
LOSS
Actual position signal is by 0.3 mA
lower than the lowest value pro-
grammed