50
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
Menu
Abbreviationindisplay Note
DG
DP2 HRDWR. VER
DH
DP2 SFTWR. VER.
DI
DP2 BUS STATUS
BAUD SEARCH
The Profibus DP interface searches a baudrate
BAUD CONTROL
The found baudrate is monitored. Hereby the DP watchdog in the master is
not activated.
DP MODE
DP communication monitored, the DP watchdog in the master is activated
WAIT PRM
The Profibus DP interface waits for correct parameter data
WAIT CFG
The Profibus DP interface waits for correct configuration data
DATA EX
The Profibus DP interface is currently exchanging data with the master.
DP FAULT
The internal status machine has detected a fault
GC CLEAR
The Profibus DP interface has received a Global Control “CLEAR” telegram. In this
state the actuator can not be operated from REMOTE.
DATA WITH LENGTH 0
The Profibus DP interface receives data with length 0 (FailSafe telegrams)
CHANNEL 2 ACTIVE
The Profibus DP interface communicates via the second channel.
DK
MODBUS1 HRDWR. VER.
DL
MODBUS1 SFTWR. VER.
DM
MODBUS1 BUS STATUS
DATA EX
The Modbus interface is currently exchanging data with the master.
BUS ACTIVE
There are Modbus telegrams recognised which are not intended for the actua-
tor’s address.
CHANNEL 2 ACTIVE
The Modbus interface communicates via the second channel.
DN
MODBUS2 HRDWR. VER.
DO
MODBUS2 SFTWR. VER.
DP
MODBUS2 BUS STATUS
DATA EX
The Modbus interface is currently exchanging data with the master.
BUS ACTIVE
There are Modbus telegrams recognised which are not intended for the actua-
tor’s address.
CHANNEL 2 ACTIVE
The Modbus interface communicates via the second channel.