Connecting bus cables
1. Connect bus cables (refer to figures 13 and 14).
2. If the actuator is the final device in the bus segment:
Ò
Connect termination resistor for channel 1 through linking the terminals
31 – 33 and 32 – 34 (standard).
Ò
For component redundancy: Connect termination resistor for channel 2
through linking the terminals 35 – 37 and 36 – 38.
3. Connect screen largely to the cable glands.
Information
Metallic EMC cable glands have to be used to provide reliable and proper
bus cable shielding.
Figure13: Bus connection channel 1 (standard)
Figure14: Bus connection channel 2 (for component redundancy only)
21
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive
Operation instructions
with actuator controls AUMATIC ACExC 01.1 Profibus DP
31
31
34
32
32
33
B
A
B
A
31 32
B
A
Figure 13
35
35
38
36
36
37
B
A
B
A
35 36
B
A
Figure 14
£
further devices will follow
from the previous device, channel 1
¢
final device
¯
to the next device, channel 1
£
further devices will follow
from the previous device, channel 2
¢
final device
¯
to the next device, channel 2