10.2.3 Status indication S2 - warnings
Warnings are indicated at this position.
È
Description of the warnings:
NO WARNING
No warnings have occurred.
WARNING OPER.TIME
The preset running time for a travel between end position OPEN and end
position CLOSED has been exceeded.
Ò
Set the running time (
MONITOR TRIGGERS
parameter) in accordance
with the actual running time.
Ò
Check tripping behaviour of end position switches.
Ò
Check actuator mechanics.
WARNING STARTS/RUN
The preset values for max. starts/h or max. running time/h have been
exceeded.
Ò
Check modulating behaviour.
Ò
Increase dead time.
Ò
Reduce number of nominal value changes.
INTERNAL FEEDBACK
Position transmitter is not standardised.
Ò
Operate actuator into both end positions (OPEN and CLOSED).
INTERNAL WARNING
Internal warnings have occurred.
For further information:
1. Go to group
D0
: Press
C
and hold it down until diagnostic indication
D0
is displayed.
2. Go to diagnostic indication
D3
: Press
q
three times.
FEEDBACK E2 LOSS
Signal loss of position transmitter.
Ò
Check position transmitter signal.
1. Go to group
D0
: Press
C
and hold it down until diagnostic indication
D0
is displayed.
2. Go to diagnostic indication
D7
,
D8
, or
D9
: Press
q
either seven, eight,
or nine times.
Ò
Check position transmitter wiring.
Ò
Check
POSITION E2.
The setting must correspond to the wiring dia-
gram.
SETPOINT E1 LOSS
Signal loss of the set point.
Ò
Check wiring.
TORQUE E6 LOSS
Signal loss of torque source.
Ò
Check wiring.
I/O1 ANALOG IN1 LOSS
Loss of signal of the analogue input 1 of the parallel interface (only for
fieldbus/standard interface combinations).
60
Multi-turn actuator SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1 Non-Intrusive
with actuator controls AUMATIC ACExC 01.1 Profibus DP
Operation instructions
WARNING IND.
S2
NO WARNING