Service Manual
48
S
ON
Motor of indoor unit
Electric heater
ON
OFF
OFF
OFF
Heating electric valve
ON
(Figure7)
9.There are timing, sleeping, power fail memory, temperature sensing (reserved) functions under this
mode.
2.6 Swing control
1.At default, the air outlet oscillating angle of the controller is the E/F mode of the first group (to be
selected by DIP switch: ON is mode E, OFF is mode F):
Mode E:
The stepping speed switch will operate at 16MS /step and normal air oscillating will operate at 24MS/step;
The wide-open angle is 52 degree;
The range of cooling air oscillating angle is 30 degree;
The range of heating air oscillating angle is 30 degree;
The initial position of the cooling air oscillating is 30 degree backward from wide-open position, the final
position is the wide-open position;
The initial position of the heating air oscillating is 30 degree backward from wide-open position, the final
position is the wide-open position;
Mode F:
The stepping speed switch will operate at 16MS /step and normal air oscillating will operate at 24MS/step;
The wide-open angle is 60 degree;
The range of cooling air oscillating angle is 30 degree;
The range of heating air oscillating angle is 30 degree;
The initial position of the cooling air oscillating is 30 degree backward from wide-open position, the final
position is wide-open position;
The initial position of the heating air oscillating is wide-open position, the final position is 30 degree
backward from wide-open position;
2.If the sleeping button is depressed 10 times within 5 seconds and the buzzer alarms 4 times, the
oscillating angle is G/H mode (effective after next power-on, and selected with the DIP switch: ON is
mode H, OFF is mode G); If the sleeping button is depressed 10 times with 5 seconds and the buzzer
alarms 2 times, then the oscillating angle will return to E/F mode of the first group (effective after next
power-on).
Mode H:
The stepping speed switch will operate at 16MS /step and normal air oscillating will operate at 24MS/step;
The wide-open angle is 65 degree;
The range of cooling air oscillating angle is 25 degree;
The range of heating air oscillating angle is 25 degree;
The initial position of the cooling air oscillating is 25 degree backward from wide-open position, the final
position is wide-open position;
The initial position of the heating air oscillating is wide-open position, the final position is 25 degree
backward from wide-open position;
Mode G:
The stepping speed switch will operate at 8MS /step and normal air oscillating will operate at 24MS/step;
The wide-open angle is 150 degree;
The range of cooling air oscillating angle is 40 degree;
Summary of Contents for AFC-1000CF/4
Page 1: ...1 Technical Manual Fan Coil Unit Ceiling Floor Type...
Page 3: ...AUKS Fan CoilGeneral description 3 Part 1 General description 1 Nomenclature...
Page 15: ...AUKS Fan CoilUnit information 15 5 Electrical wiring and connection...
Page 22: ...AUKS Fan CoilUnit information 22 7 Explode view AFC 400CF 4 AFC 500CF 4...
Page 30: ...AUKS Fan CoilUnit information 30...
Page 53: ...Service Manual 53 6 Failure analysis Wired controller communication failure...
Page 54: ...Service Manual 54 Drainage system failure...
Page 55: ...Service Manual 55 No action after power on...
Page 56: ...Service Manual 56 Poor Performance during Unit Operation...
Page 57: ...Service Manual 57...
Page 58: ...Service Manual 58 Abnormal sound or vibration...
Page 59: ...Service Manual 59 Abnormal odor...
Page 60: ...Service Manual 60 Air conditioner water leakage...