AUKS Fan CoilUnit information
11
variable working condition performance parameter table (continued)
Unit: W
Air inlet temperature
℃
27
℃
DB/19. 5
℃
WB
28
℃
DB/22
℃
WB
Water inlet temperature
℃
5
7
9
5
7
9
Model
(CFM)
Water
flow
(kg/h)
Water
pressure
drop
(kPa)
TH
SH
TH
SH
TH
SH
TH
SH
TH
SH
TH
SH
400
430
8.1
2714
2012
2403
1863
2213
1856
3402
2522
3078
2386
2781
2062
550
11.5
3119
2255
2768
2079
2410
1971
3902
2821
3551
2668
3200
2313
650
15.5
3699
2430
3267
2228
2849
2112
4577
3006
4199
2863
3780
2483
750
20
4037
2511
3618
2282
3161
2140
5063
3149
4617
2911
4131
2570
500
600
18
3385
2510
2998
2324
2761
2316
4244
3146
3840
2977
3470
2572
700
24
3891
2813
3453
2594
3007
2458
4868
3519
4430
3328
3992
2886
800
30
4615
3032
4076
2779
3555
2635
5710
3751
5238
3571
4716
3098
900
37
5036
3133
4514
2847
3944
2671
6316
3929
5760
3632
5154
3206
600
750
21.5
4055
3006
3591
2784
3307
2774
5084
3769
4600
3566
4156
3081
850
26.8
4659
3369
4135
3106
3600
2944
5829
4214
5305
3985
4780
3456
950
32.7
5528
3631
4882
3329
4258
3156
6839
4493
6274
4278
5649
3711
1050
39
6031
3752
5406
3409
4723
3198
7564
4706
6899
4350
6173
3840
800
900
14.8
5988
4439
5303
4111
4883
4096
7508
5565
6793
5266
6137
4549
1100
21
6883
4976
6108
4588
5318
4349
8611
6225
7836
5887
7061
5105
1300
28
8163
5363
7210
4916
6288
4661
10100
6635
9266
6318
8342
5480
1500
36
8909
5542
7985
5035
6976
4724
11173
6950
10190
6426
9117
5672
1000
1200
23
7490
5552
6633
5142
6108
5124
9391
6961
8496
6587
7676
5690
1400
30
8608
6223
7639
5739
6652
5439
10769
7785
9800
7362
8831
6385
1600
38
10210
6708
9018
6149
7865
5830
12633
8299
11589
7902
10434
6854
1800
46.8
11142
6931
9987
6298
8726
5908
13974
8693
12745
8037
11403
7094
Summary of Contents for AFC-1000CF/4
Page 1: ...1 Technical Manual Fan Coil Unit Ceiling Floor Type...
Page 3: ...AUKS Fan CoilGeneral description 3 Part 1 General description 1 Nomenclature...
Page 15: ...AUKS Fan CoilUnit information 15 5 Electrical wiring and connection...
Page 22: ...AUKS Fan CoilUnit information 22 7 Explode view AFC 400CF 4 AFC 500CF 4...
Page 30: ...AUKS Fan CoilUnit information 30...
Page 53: ...Service Manual 53 6 Failure analysis Wired controller communication failure...
Page 54: ...Service Manual 54 Drainage system failure...
Page 55: ...Service Manual 55 No action after power on...
Page 56: ...Service Manual 56 Poor Performance during Unit Operation...
Page 57: ...Service Manual 57...
Page 58: ...Service Manual 58 Abnormal sound or vibration...
Page 59: ...Service Manual 59 Abnormal odor...
Page 60: ...Service Manual 60 Air conditioner water leakage...