Service Manual
52
resistance approximately equal), resistance of winding should be infinite.
5. DIP setting and failure code
5.1 Dip setting of the control panel
The DIP switch of the controller has a setting condition that varies with different models. The DIP switch
was already adjusted in the factory of the company, but the service personnel of the user shall take care
during the service process.
Function introduction of the DIP functions of the unit
DIP switch
Function
ON
OFF
Default
Remark
3 DIP-1
Coupling
Coupled switch
No
OFF
3 DIP-2
Air oscillation
mode
Mode E
Mode F
ON
Mode H
Mode G
3 DIP-3
Valve selection
Single valve
Cold and heat
water valves
ON
Note: Mode E is applicable to model C7 ceiling unit(MB12 panel), mode F applicable to model 120 ceiling
unit(MB06 panel), model G applicable to ceiling floor unit, mode H applicable to model C7 ceiling
unit(MB13 panel).
DIP switch
Function
ON
OFF
Default
Remark
4 DIP-1
-
-
-
-
4 DIP-2
Water level
switch protection
Protection
shielded
Protection
normal
ON
4 DIP-3
Power fail
memory
Yes
No
OFF
4 DIP-4
Heating
selection
Single electric
heating
Water
valve+electric
heating
OFF
When water
valve+electric heating
are operating, the
electric heating will be
automatically activated
The system presume that under single valve, cooling, and heating mode, the water valve outputs via
cooling valve, so in the specifications: If a single valve model is selected, the heating and the heating
valve action under AUTO mode are achieved through the cooling valve; If a cold/hot water valve model,
the heating and the heating valve action under AUTO mode are achieved through the heating valve;
Electric heating can only be used on units without coupled switches.
5.2 Failure code display
When the air conditioner is faulty, the timing light of the controller’s light panel will display relevant trouble
codes according to various troubles.
Failure cause
Display method 1
Display method 2
Display
priority
Phenomenon
Communication failure
Timing light flashes 5 times/8s
E5
1
Stop
Drainage system failure
Timing light flashes 4 times/8s
E4
2
Stop
Return temperature sensor failure
Timing light flashes once/8s
E1
3
Stop
Summary of Contents for AFC-1000CF/4
Page 1: ...1 Technical Manual Fan Coil Unit Ceiling Floor Type...
Page 3: ...AUKS Fan CoilGeneral description 3 Part 1 General description 1 Nomenclature...
Page 15: ...AUKS Fan CoilUnit information 15 5 Electrical wiring and connection...
Page 22: ...AUKS Fan CoilUnit information 22 7 Explode view AFC 400CF 4 AFC 500CF 4...
Page 30: ...AUKS Fan CoilUnit information 30...
Page 53: ...Service Manual 53 6 Failure analysis Wired controller communication failure...
Page 54: ...Service Manual 54 Drainage system failure...
Page 55: ...Service Manual 55 No action after power on...
Page 56: ...Service Manual 56 Poor Performance during Unit Operation...
Page 57: ...Service Manual 57...
Page 58: ...Service Manual 58 Abnormal sound or vibration...
Page 59: ...Service Manual 59 Abnormal odor...
Page 60: ...Service Manual 60 Air conditioner water leakage...