GENERAL DESCRIPTION
710-13019-00A
MVS User Manual
Page 5
2.1
Overview
The MVS provides compact and robust soft start solutions for control of medium voltage motors. MVS soft starters
provide a complete range of motor and system protection features and have been designed for reliable performance in the
most demanding installation situations.
Each MVS soft starter comprises two elements:
a power assembly
a controller module
The power assembly and controller module are supplied as a pair and share the same serial number. Care should be
taken during installation to ensure the correct controller and power assembly are used together.
Each MVS is also supplied with two fibre-optic cables, to connect the controller module to the power assembly, and three
non-conduction lead assemblies, allowing the soft starter to be tested with a low-voltage motor (< 500 VAC).
2.2
Feature List
Starting
Constant current
Current ramp
Stopping
Coast to stop
Soft stop
Protection
Under/ Overvoltage
Mains frequency
Phase sequence
Shorted SCR
Motor overload (thermal model)
Instantaneous overcurrent (two stages)
Time-overcurrent
Ground fault
Undercurrent
Current imbalance
Motor thermistor
Excess start time
Power circuit
Auxiliary trip
Extensive input and output options
Remote control inputs
(3 x fixed, 2 x programmable)
Relay outputs
(3 x fixed, 3 x programmable)
Analog output
(1 x programmable)
Serial port (with module)
Comprehensive feedback
Starter status LEDs
Date and time stamped event logging
Operational counters (starts, hours-run, kWh)
Performance monitoring (current, voltage, power factor,
kWh)
User-programmable monitoring screen
Multi-level password protection
Emergency stop push button
Power Connection
50 A to 600 A, nominal
2300 VAC to 7200 VAC
Accessories (optional)
DeviceNet, Modbus or Profibus communication modules
Synchronous motor control
PC Software
Overvoltage protection
Control supply transformer
MV/LV Control transformer
Section 2
General Description