COMMISSIONING
710-13019-00A
MVS User Manual
Page 43
1.
Open the Commissioning Menu.
2.
Scroll to Output Signalling Simulation and press .
3.
Use the
and
buttons to select a function to simulate, then press
.
4.
Use
the
and
buttons
to
turn the signal on and off.
To confirm correct operation, monitor the state of the output.
Prog Relay A
Off
On
5.
Press to return to the simulation list.
Analog Output Simulation
The analog output simulation uses the and buttons to change the
analog output current at terminals B10, B11 of the Controller.
Analog Output
0% 4
mA
Attach an external current measuring device to terminals B10, B11 of the Controller. Use the or button to adjust
the percentage value in the lower left hand corner of the display. The current measuring device should indicate the same
level of current as shown at the lower right corner of the display.
Temperature Sensors State
This screen shows the state of the motor thermistors and RTD/PT100s.
Temp Sensors State
Thermistor: O
RTDs A–
>
G:OOOOOOO
S = shrt H=hot C=cld O=opn
NOTE
The use of RTDs is not supported by this product and this screen will always indicate Open = o.
Digital I/O State
This screen shows the current status of the digital inputs and outputs.
Digital I/O State
Inputs: 1000000
Outputs: 0000000
The top line of the screen shows the start, stop, reset and programmable inputs A and B, then '00'. The screen shows input
C23~C24 closed with all other inputs open.
The bottom line of the screen shows programmable output A, the fixed Run output, programmable outputs B and C, then
'000'. The screen shows all outputs open.
Analog I/O State
This screen shows the current status of the Analog I/O
Analog I/O State
Input: - - - - %
Output A: 04.0mA
NOTE
Input is not supported by this product and this screen will always indicate Input: - - - - %
Reset Thermal Models
The MVS's advanced thermal modelling software constantly monitors the motor's performance. This allows the MVS to
calculate the motor's temperature and ability to start successfully at any time.
The thermal model for the active motor can be reset if required.
1.
Open the Commissioning Menu..
2.
Scroll to Reset Thermal Models and press .
3.
At the confirmation prompt press STORE to confirm or to
cancel the action. You may have to enter your access code.
Reset Thermal Models
M1
X%
M2
X%