PROGRAMMING MENU
710-13019-00A
MVS User Manual
Page 37
Parameter 8L
Graph Minimum Adjustment
Range:
0% – 600%
Default: 0%
Description:
Adjusts the lower limit of the performance graph.
8M – Current Calibration
Range:
85% - 115%
Default:100%
Description:
Calibrates the soft starter's current monitoring circuits to match an external current metering
device.
Use the following formula to determine the necessary adjustment:
Calibration (%) =
Current shown on MVS display
Current measured by external device
eg 102% =
66A
65A
NOTE
This adjustment affects all current-based functions and protections.
8N – Mains Ref Volt
Range:
100 – 14000 V
Default: 400
V
Description:
Provides the reference voltage for the analog output and performance graphs.
8O – Voltage Calibration
Range:
85% – 115%
Default: 100%
Description:
Adjusts the soft starter's voltage monitoring circuits. The MVS is factory-calibrated with an
accuracy of ± 5%. This parameter can be used to adjust the voltage readout to match an
external voltage metering device.
Set
as
required,
using
the following formula:
Calibration (%) =
Voltage shown on soft starter display
Voltage measured by external device
eg 90%
6000
6600
NOTE
This adjustment affects all voltage-based functions.
9 Motor Data-2
The MVS can support two different starting and stopping motor data sets.
To select the secondary motor data set, a programmable input must be configured to parameter set selection (parameters
6A and 6F) and the input must be active when the soft starter receives a start signal.
NOTE
You can only choose which motor data set to use while the soft starter is stopped.
9A ~ 9E – Secondary Motor Settings
Parameter 9A
Reserved
This parameter is reserved for future use.
Parameter 9B
Motor FLC-2
Range:
5 - 1000 A
Default:100 A
Description:
Sets the secondary motor's full load current.
Parameter 9C
Reserved
Description:
This parameter is reserved for future use.
Parameter 9D
Reserved
This parameter is reserved for future use.