APPENDIX
710-13019-00A
MVS User Manual
Page 63
EEPROM fail
23
23
62
Input B trip
24
24
110
Bypass fail
25
25
105
L1 phase loss
26
26
23
L2 phase loss
27
27
24
L3 phase loss
28
28
25
L1-T1 shorted
29
29
115
L2-T2shorted 30
30
116
L3-T3 shorted
31
31
117
Battery/Clock 35
35
121
Miscellaneous n/a
n/a
70
No trip
255
255
0
PC Software
WinMaster is a purpose-designed software suite for control and monitoring a soft starter. WinMaster is compatible with
all AuCom soft starter ranges and is ideal for parameter management during commissioning. WinMaster has the following
features:
Operational control (Start, Stop, Reset, Quick Stop)
Starter status monitoring (Ready, Starting, Running, Stopping, Tripped)
Performance monitoring (motor current, motor temperature)
Upload parameter settings
Download parameter settings
To use WinMaster with the MVS, the soft starter must be fitted with a USB Module (PIM-USB-01) or a Modbus Module
(PIM-MB-01).
Other MVS Accessories
Other accessories available to enhance your MVS starter include:
RTD protection relay
Motor protection relay (external to MVS)
Power meter
Indication lamps
Start, stop and reset pushbuttons
Local/remote selector switch
Internal panel light for low voltage section
Panel heater
Power supply and contactor for motor heater
Control transformers
Metering VT
MV/LV control supply transformer
NOTE
Other accessories may be available on request.
R Rated Protection Fuses
If specified, R Rated protection fuses can be installed on the supply side of the soft starter to provide Type 2 coordination
and short circuit protection for the motor branch circuit. The appropriate fuse should be selected from the table below,
based on the motor's rated full load current. MVS models V02 ~ V07 must be installed with fuses.
Fuse ratings:
Starter Rated FLC
Fuse
80 A
6R
159 A
12R
230 A
18R
321 A
24R