ALARM SPIRAL
Failure of both the ignition spi-
rals
Check and replace both the
ignition spirals and check and
replace faulty fuses (3.15 A) on
the electronic board
Enter the activation code:
1234
10
ALARM START
All the allowed start (ignition)
attempts have been exhausted
There are no more pellets or the
bin is empty
Faulty ignition spirals
Faulty photocell
Replenish fuel, draw pellets to
the conveyor and turn of and
on the main switch on the boil-
er
Check the supply wires of the
ignition spirals, check the fus-
es (3.15 A), check the ignition
elements with the function in
the TESTING menu
Check the supply cable of the
photocell with the connector,
test the photocell with the use
of the function in the TEST-
ING menu
11
ALARM
PHOTOCELL
Flame sensing error in the OP-
ERATION mode
Clean the photocell
If necessary, replace
CAUTION
– In case of the
ALARM SPIRAL
error message you must always replace
both the ignition spirals and enter the
activation code 1234
. If after the replacement of the
ignition spirals and entering of the code the burner does not ignite (no ignition element is
heating), replace the AC07X electronic control unit and use the reserve output for full con-
trol of one ignition spiral. In such a case set the parameter
S6 = 5 or S14 = 5
.
.
Summary of Contents for A85
Page 1: ...Operation and Maintenance Manual EN www atmos cz Operation and Maintenance Manual ...
Page 2: ...www atmos cz Operation and Maintenance Manual EN ...
Page 61: ...Operation and Maintenance Manual EN EN www atmos cz EN 61 20 Expanded view of the burner ...
Page 66: ...EN www atmos cz 66 EN Operation and Maintenance Manual EN Notes ...