background image

M0394

86C

B

  Rel 0.0 0

6

/20

20

BURNERS - BRUCIATORI - BRULERS - BRENNER - QUEMADORES - 

ГОРЕЛКИ

MANUAL OF INSTALLATION - USE - MAINTENANCE

RX92-FGR

RX92R-FGR

RX512-FGR

RX512R-FGR

RX515-FGR

Gas burners

LAMTEC BT3xx

Microprocessor-controlled

Summary of Contents for LAMTEC BT3 Series

Page 1: ...6CB Rel 0 0 06 2020 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES MANUAL OF INSTALLATION USE MAINTENANCE RX92 FGR RX92R FGR RX512 FGR RX512R FGR RX515 FGR Gas burners LAMTEC BT3xx Microprocessor contr...

Page 2: ...e employed exclusively for the use for which it was designed Before connecting the burner make sure that the unit rating is the same as delivery mains electricity gas oil or other fuel Observe caution...

Page 3: ...gaseous fuels 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Directive 2006 42 EC Machinery Directive Harmonized standards UNI EN 676 Automatic forced draught burners for ga...

Page 4: ...s oil and solid fuel burning appliances having electrical connections UNI EN ISO 12100 2010 Safety of machinery General principles for design Risk assessment and risk reduction National Standard UNI 7...

Page 5: ...This one for ces the pressure in the utilisation limits The actuators move proportionally the air damper and the gas butterfly valve in order to achieve the optimisation of the gas flue values as to g...

Page 6: ...L Extended 5 DESTINATION COUNTRY see data plate 6 BURNER VERSION A Standard Y Special 7 EQUIPMENT 1 2 gas valves gas proving system 8 2 gas valves gas proving system maximum gas pressure switch 8 GAS...

Page 7: ...as pressure see gas curves Note3 Burners are suitable only for indoor operation with a maximum relative humidity of 80 GAS CAT COUNTRY I2H AT ES GR SE FI IE HU IS NO CZ DK GB IT PT CY EE LV SI MT SK B...

Page 8: ...085 439 261 291 228 447 360 464 M12 424 280 310 300 790 148 642 478 55 481 170 200 549 9 131 RX92 FGR 50 1349 1459 135 35 550 100 420 530 493 868 506 1274 725 439 286 316 228 450 360 464 M12 424 280 3...

Page 9: ...512 FGR 1 50 VISTA A A 766 527 226 845 946 609 532 517 973 494 35 540 390 540 390 P347 390 390 552 614 149 270 496 190 1512 1555 529 62 P151 P225 P195 14 M 594 P 309 460 60 44 558 311 2 2 5 4 5 P9 FGR...

Page 10: ...FGR 1 65 VISTA A A 540 390 540 390 P400 390 390 552 P151 P225 P195 14 M 2 2 5 4 5 P9 558 44 532 529 967 650 844 447 609 1577 270 499 769 62 360 494 611 530 222 969 1512 61 35 149 487 291 356 FGR FLANG...

Page 11: ...ailable gas pressure value upstream the burner s gas valve Then subtract the backpressure The result is called pgas Draw a vertical line matching the furnace input value 600kW in the example quoted on...

Page 12: ...imum output point is usually reached by adjsuting the combustion head to its MAX position see paragraph Adjusting the combustion head the minimum output point is reached setting the combustion head to...

Page 13: ...sary to get the requested gas rate add the pressure value in the combustion chamber to the value read on the y axis The values in the diagrams refer to natural gas with a calorific value of 8125 kcal...

Page 14: ...utlet on the combustion chamber 3 Gas pressure outlet on the butterfly valve 4 Differential pressure gauge Measuring gas pressure in the combustion head In order to measure the pressure in the combust...

Page 15: ...es in the diagrams refer to natural gas with a calorific value of 8125 kcal Stm3 15 C 1013 mbar and a density of 0 714 kg Stm3 The values in the diagrams refer to GPL with a calorific value of 22300 k...

Page 16: ...Do not stand under lifted loads Packing The burners are despatched in wooden crates whose dimensions are 9xA series 1600mm x 1180mm x 860mm L x P x H 5xxA series 1886mm x 1456mm x 1120mm L x P x H Pa...

Page 17: ...refractory cement RX512R FGR RX515 FGR Fitting the burner to the boiler To perform the installation proceed as follows 1 drill the furnace plateas decribed in paragraph Overall dimensions 2 place the...

Page 18: ...essure in combustion chamber are included in the burner performance curve otherwise the choice of the burner must be revised consulting the burner manufacturer To choose the blast tube lenght consider...

Page 19: ...is obtained in a plant designed according to the following guidelines size the FGR pipe as per the example below ATTENTION Pipe elbows increase pressure losses so limit their use as much as possible...

Page 20: ...wing diagrams make sure bolts on the flanges are properly tightened Key WARNING before executing the connections to the gas pipe network be sure that the manual cutoff valves are closed ATTENTION it i...

Page 21: ...raneous material drops inside the valves during maintenance and cleaning operation of the filters both the filters outside the valves group and the ones built in the gas valves WARNING Slowly open the...

Page 22: ...ncludes a vent limiter according to UL 353 and ANSI Z21 18 CSA 6 3 No venting required in locations where vent limiters are accep ted by the jurisdiction 4 Only PS pressure sensors specified by DUNGS...

Page 23: ...rmally installed upstream from all the control and on off devices Once the train is installed connect the gas valves group and pressure switches plugs Caution the SKP2 diaphragm D must be vertical see...

Page 24: ...between EV1 and EV2 The PGMIN LT pressure switch senses the pressure which remains present and stable and closes the contact giving consent to continue the cycle to the equipment Case B presence of p...

Page 25: ...0 V supply and in the case of three phase 220 V or 230 V supply it is necessary to modify the electrical connections into the terminal box of the electric motor and replace the overload tripped relay...

Page 26: ...CE TO SECURE THE MACHINE ACT ON THE ISOLATOR SWITCH IN CASE OF ANOMALIES THAT REQUIRED A SHUT DOWN OF THE BURNER IT S POSSIBLE TO ACT ON THE AUXILIARY LINE SWITCH LOCATED ON THE BURNER FRONT PANEL IN...

Page 27: ...ner staring cycle begins in case of leakage in a valve the gas proving system stops the bur ner and the lamp B1 turns on At the beginning of the start up cycle the actuator drives the air damper to th...

Page 28: ...e is at least equal to the pressure required by the pressure curves burnt gas flow Adjustments brief description The air and fuel rates adjustments must be performed at the maximum ouptput first high...

Page 29: ...home page keep thermostat open Burner remain in stand by Unlock the controller press ENTER Info Press the right key to position on the Settings icon indicated with wrench and hammer Press ENTER Manual...

Page 30: ...click to EDIT Press ENTER to enter the curves page Keep the password 0000 and confirm with ENTER Air gas position at burner s ignition 1 ignition position 2 air servomotor position digit 1 gas servom...

Page 31: ...es not start with those settings the chap ter SETTING THE IGNITION POINT WITH BURNER IN STAND BY In case of troubles the burner will go on lock out mode and the reason will be indicated on the display...

Page 32: ...the lock code press ENTER to unlock Press ENTER to modify the positions burner in stand by Click up to increase the gas opening position or down to decrease it Clickup to increase the air opening posi...

Page 33: ...modify the combustion valves and adjust servomo tors position gas and air press ENTER Click up to increase the gas opening position or down to decrease it Right click to move from gas servomotor adju...

Page 34: ...BURNER IN STAND BY Set the maximum load position 999 according to the maximum output required by the boiler If necessary set the inlet gas pressure at the exit of the gas pres sure reducer Check the o...

Page 35: ...e CAUTION The fuel air calibration procedure is the same for both gas and diesel In the display will be indicated Gas or Diesel Press EXIT again to quit main menu Press EXIT again to quit settings The...

Page 36: ...justments do not exceed a value that creates a hazardous condition to the burner Adjusting output pressure for positive pressure systems requires PS 10 40 or PS 50 200 Outlet pressure MIN 10 25 50 75...

Page 37: ...ed To calibrate the maximum pressure switch proceed as follows according to its mounting position remove the pressure switch plastic cover if the maximum pressure switch is mounted upstreaam the gas v...

Page 38: ...e VB screw and slightly move the combustion head backwards turning clockwise the knob VRT Fasten VB screw when the adjustment is accomplished Depending on the boiler application it is possible to act...

Page 39: ...and clean the combustion head Examine and clean the ignition electrodes adjust and replace them if necessary Examine and clean the detection electrode photoelement according to the burner models repl...

Page 40: ...ombustion head reverse the procedure described above having care to place correctly the O ring OR between burner and gas manifold DANGER Do not invert the servomotor cables Attention before adjusting...

Page 41: ...nition and detection electrodes to contact metallic parts blast tube head etc other wise the boiler s operation would be compromised Check the electrodes position after any intervention on the combust...

Page 42: ...ead ATTENTION avoid the electrode to get in touch with metallic parts blast tube head etc otherwise the boiler operation would be compromised Check the electrode position after any intervention on the...

Page 43: ...strictly prohibited Seasonal stop To stop the burner in the seasonal stop proceed as follows 1 turn the burner main switch to 0 Off position 2 disconnect the power mains 3 close the fuel valve of the...

Page 44: ...tch damaged or bad links Check air pressure switch functions and links Burner control damaged Replace burner control BURNER LOCKS OUT WITHOUT ANY GAS FLOW Gas valves don t open Check voltage on valves...

Page 45: ...PART IV MAINTENANCE 45 WIRING DIAGRAMS Refer to the attached wiring diagrams WARNING 1 Electrical supply 230V 400V 50Hz 3N a c 2 Do not reverse phase with neutral 3 Ensure burner is properly earthed...

Page 46: ...PART IV MAINTENANCE 46...

Page 47: ......

Page 48: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Page 49: ...Quick Guide SISTEMA DI CONTROLLO ELETTRONICO ELECTRONIC CONTROLSYSTEM SISTEMA DE CONTROL ELECTR NICO SYST ME DE CONTR LE LECTRONIQUE LAMTEC BT 3xx M12929CA 05 2018...

Page 50: ...UTPUTS 14 3 2 MANUAL MENU PATH 16 3 2 1 Regolazione manuale carico bruciatore 16 3 3 SETTINGS MENU PATH 17 3 3 1 ENTER PASSWORD 17 3 3 2 PROGRAM SEQUENCE 18 Set duration of pre purge 18 Set duration o...

Page 51: ...E WITH VSD optional 45 This Guide for quick start up summarises the basic operations that are necessary to start up and set the BT control unit The information contained here do NOT replace the user m...

Page 52: ...ursor keys Enter key For to confirm the value or operation 2 2 MENU FUNCTIONST Information Select the INFO path for information about the following the burner errors that have occurred the software ve...

Page 53: ...put at connector X10 2 It is for this reason that the burner will turn off only with the intervention of the safety chain connector X07 which will send it in lock out Settings Select the SETTINGS path...

Page 54: ...SETTINGS menu path 7 Window number 3 1 INFORMATION MENU PATH 3 1 1 INFORMATION PATH Use the cursor keys to select the path and confirm this with Enter 1 Selected burner information selected 2 Serial...

Page 55: ...operating hours selected 2 Number of burner start ups Use the cursor keys to select the path and confirm this with Enter The display shows the Display operating hours menu window 1 Pictogram operatin...

Page 56: ...menu window 1 Pictogram burner start up 2 Number of burner start ups oil operation 3 Number of burner start ups gas operation 3 1 4 RECALL FAULT HISTORY From the home screen use the cursor keys to se...

Page 57: ...and confirm this with Enter 1 Error code display pictogram 2 Fault code the last 10 faults are stored in which no 01 is the most recent fault 3 Diagnostic code 1 4 Diagnostic code 2 5 Number of operat...

Page 58: ...ter 1 Check sums pictogram 2 Check sum access level 0 3 Check sum access level 1 4 Check sum access level 2 5 Check sum access level 4 CRC16 CHECK SUMS The check sums are formed from the device parame...

Page 59: ...S OF ACTUATING DRIVES From main page see paragraf 2 4 use the cursor keys to select the path and confirm this with Enter 1 Actuating drive pictogram 2 Actuating drive channel 1 air 3 Actuating drive c...

Page 60: ...puts pictogram Select the menu and confirm this with Enter Page 1 of inputs menu 1 Digital inputs pictogram 2 Jump to next page 3 Fuel selection oil no 4 Fuel selection gas yes 5 Burner start yes term...

Page 61: ...e 3 of inputs 1 Digital inputs pictogram 2 Jump to previous page 3 Jump to next page 4 Safety interlock chain oil closed no terminal X06 5 Safety interlock chain gas closed no 6 Safety interlock chain...

Page 62: ...r keys to select and confirm this with Enter Page 1 digital outputs 1 Digital outputs pictogram 2 Jump to next page 3 Fan on terminal X25 4 Error off terminal X24 adjustable with P 809 5 Ignition tran...

Page 63: ...valve on terminal X03 5 Gas valve 1 off terminal X01 6 Gas valve 2 off terminal X02 Use the cursor key to select the next page and confirm this with Enter Page 4 digital outputs 1 Digital outputs pic...

Page 64: ...e switches off the burner when you exit the menu If the burner is switched on manually via display the BT300 no longer responds to the Burner ON signal input at connector X10 2 It is for this reason t...

Page 65: ...SWORD Warning Password level 0 setting view Password level 1 change curve points Password level 2 changing burner parameter settings pre purge gas leakage burner parameter PID etc Use the cursor keys...

Page 66: ...OF PRE PURGE Use the cursor keys to select and confirm this with Enter 1 Duration of pre purge pictogram 2 Pre purge time set 3 Accept value by pressing Enter The countdown starts for to confirm the...

Page 67: ...mber UI300 4 Parameter number BT300 5 Pictogram discard parameters 6 Value for BT300 7 Value for UI300 If both values are equivalent the value can be accepted by pressing Enter If there is a discrepan...

Page 68: ...lay shows the Duration of post purge 1 Duration of post purge pictogram 2 Set duration of post purge 3 Accept setting by pressing Enter Use the cursor keys to select the number you wish to change Chan...

Page 69: ...The valve leakage test is set Accept or discard the entry Access level 2 is required to set this function CHECK VALVE LEAKAGE TEST AFTER FLAME OFF Use the cursor keys to select and confirm this with...

Page 70: ...with Enter Accept or discard the entry Access level 2 is required to set this function ACTIVATE THE PILOT BURNER IN GAS OPERATION Use the cursor keys to select and confirm this with Enter Change the...

Page 71: ...or discard the entry Access level 2 is required to set this function CONFIGURATION OF ACTUATING OUTPUTS Use the cursor keys to select and confirm this with Enter Configuration of actuating outputs men...

Page 72: ...tuator position Use the cursor keys to switch to the next channel Use the cursor keys to set actuator s position in the selected firing rate point Set the position of the actuator at the desired combu...

Page 73: ...rves selected 3 Confir deletion of curves The display shows the confirmation prompt Confirmation prompt of the delete curves menu 1 Back to previous menu 2 Delete values selected 3 Proceed with deleti...

Page 74: ...n saver 3 4 OTHER DISPLAYS NO CONNECTION BETWEEN UI300 AND BT300 No connection 1 UI300 user interface pictogram 2 Symbol for no connection 3 BT300 burner control Display shown e g when using the LSB r...

Page 75: ...fall short for to long Channel x 211 Second monitoringband exceeded for to long Channel x 221 Second monitoring band fall short for to long Channel x 231 Fuel air ratio control is blocked Channel x 2...

Page 76: ...ation 734 Pre ventilation period falls below the minimum 739 Leakage test Main gas valve 2 opens for too long 740 Leakage test Main gas valve 1 leaky 741 Leakage test Main gas valve 1 opens for too lo...

Page 77: ...diagnosis error possible cause of error BurnerTronic 988 Fuel selection relay in the DFM is defective or inconsistent 989 Plausibility test of actuator feedback in programmed curve failed 990 Power fa...

Page 78: ...rminal for fan or transformer available 32 Necessary outputs for operation with oil not available Oil pump or oil valve 33 Necessary outputs for operation with gas not available gas valve 34 An output...

Page 79: ...area is no multiple of 3 242 uiEEStartAddr Write beyond end of non safety area 243 uiEEStartAddr Start address is in reserved area 244 ulReqFIFOSpace Not enough FIFO space 250 ulong32 pucDst Readback...

Page 80: ...ress 700 0 CPU selftest failed 701 sSelftest sMngr eState state event machine failed with AC_ERR 710 sSelftest sWD eErrorState Watchdog selftest failed 711 sSelftest sWD eState Invalid default case 72...

Page 81: ...ID_DIRECTION 1471 psActuator ucSANumber U_SA_FEEDBACK_INVALID_DIRECTION 1472 psActuator ucSANumber U_SA_FEEDBACK_WRONG_FEEDBACK 1480 psActuator ucSANumber U_SA_REFERENCE_SEARCH_INVALID_ACTUATOR_TYPE 1...

Page 82: ...ll errors for which no error number was registered 3100 Error message of a password module 3101 Error message of the password module 3200 Internal overflow intermediate result does not fit in the vari...

Page 83: ...sferred channel number out of the permitted range 4705 ucKnr Transferred channel number out of the permitted range 4706 ucKnr Transferred channel number out of the permitted range 4707 ucKnr Transferr...

Page 84: ...points index firing rate point in original curve invalid 6208 Original curve points index invalid point index 6209 0 Point approximation not possible no prior point 6210 0 Point approximation not poss...

Page 85: ...CURVE Initial home page keep thermostat open Burner remain in stand by Unlock the controller press ENTER Info Manual Setting Press the right key to position on the Settings icon indicated with wrench...

Page 86: ...38 Press ENTER again after selecting the key icon Keep the password 0000 and confirm with ENTER New page level 1 unlocked Right click to EDIT Press ENTER to enter the curves page...

Page 87: ...URNER Close the thermostat the burner starts Pre purge The controller moves the servomotors to the ignition position and excites the ignition transformer If the burner starts with those settings this...

Page 88: ...the reason will be indicated on the display Check the lock code press ENTER to unlock Press ENTER to modify the positions burner in stand by Click up to increase the gas opening position or down to d...

Page 89: ...41 Clickup to increase the air opening position or down to decrease it Press ENTER to save the new settings CLOSE THE THERMOSTAT LINE GAS AIR GAS AIR...

Page 90: ...tors position gas and air press ENTER Click up to increase the gas opening position or down to decrease it Right click to move from gas servomotor adjustment to air servomotor adjustment Click up to i...

Page 91: ...e maximum load position 999 according to the maximum output required by the boiler If necessary set the inlet gas pressure at the exit of the gas pressure reducer Check the output combustible and the...

Page 92: ...e display Exemple H009 lock out code D1 diagnostic 1 D2 diagnostic 2 xxh operation hours Check the lock code press ENTER to unlock If the ignition setting is not good enough e g too much air the burne...

Page 93: ...VSD OPTIONAL With VSD modify the curve points only with burner on With burner on STANDBY press Enter With the arrows go on the icon press Enter With the arrows go on the icon press Enter Check the pas...

Page 94: ...46 With the arrows go on the icon press Enter press Enter to cancel the curve press Enter to confirm curve cancellation Now the working curve has been cancelled press Enter press Exit...

Page 95: ...s go on the icon press Enter Close the thermostat line The burner carries out the pre purge The burner reaches the ignition point Wait for the air gas servomotors to reach 0 degrees The VSD is set at...

Page 96: ...s and press Enter press Enter to confir the ignition point the burner discharges and opens the valves With burner on check the combustion with a combustion analyser Modify using the arrows and press E...

Page 97: ...firm Press to move onto the maximum load 999 press Enter Press to set the maximum burner output Press Enter to confirm Check the combustion in all curve points 800 700 600 500 400 300 250 as in previo...

Page 98: ......

Page 99: ......

Page 100: ......

Page 101: ...y logic continuous 0 10V Rload 250K 0 4 20mA Rload 500 Control outputs on off Maximum power limit heat cool 0 0 100 0 C F selection configurable from faceplate Linear scale ranges 1999 to 9999 with co...

Page 102: ...eld is reached the value will not change even if the key remains pressed Automatic Manual adjustment selection Active only when PV display visualises the process variable button pressed for at least 5...

Page 103: ...ed INF InP Out PAS 99 Pro Lin Input settings Output settings Hardware configuration Input linearization NO Keep the F key pressed to scroll the menus Release the F key to select the displayed menu Pre...

Page 104: ...min digit sec see SP r Antireset Feedforward 0 9999 scale points 100 0 100 0 Reset power 100 0 100 0 Softstart time 0 0 500 0 min LBA alarm may be reset by simultaneously pressing keys when OutP is di...

Page 105: ...32 3182 32 0 999 9 6 TC S C 0 1750 0 0 999 9 7 TC S F 32 3182 32 0 999 9 8 TC T C 200 400 199 9 400 0 9 TC T F 328 752 199 9 752 0 28 TC CUSTOM CUSTOM 29 TC CUSTOM CUSTOM 30 PT100 C 200 850 199 9 850...

Page 106: ...ntrol type 0 disabled 1 V0 Heat action 3 V3 Heat action 8 valve manual control with Raise and Lower keys ac t dE b Actuator travel time time employed by the valve to change from entirely open to entir...

Page 107: ...I heat 4 5 6 PID heat 7 8 9 ON OFF heat 10 11 12 13 14 Selection of derivative action sampling time 0 sample 1 sec 16 sample 4 sec 32 sample 8 sec 64 sample 240 msec Note LbA alarm is not enabled with...

Page 108: ...g scale s 33 s 00 Lin Lin Custom linearization for main input the n step value corresponds to input mV beginning scale n mV mV mV full scale mV beginning scale 32 Step 0 beginning of scale value Step...

Page 109: ...entially at firing Ramp 0 phase Enabled by setting GS 0 0 Starting from setpoint PV initial state it reaches pre heating set SP 0 with gradient GS 0 Maintenance phase Enabled by setting Ht 0 0 Maintai...

Page 110: ...ue Minimum impulse t Lo expressed as a of the actuator time resolution 0 1 Represents the minimum change in position corresponding to a minimum change in power supplied by the instrument below which t...

Page 111: ...of the integral The frequency and duration of the impulses is correlated to the integral time h it or c it Non movement behavior t Hi 0 with power 100 or 0 0 the corresponding open or close outputs a...

Page 112: ...e gradient 12 SET GRADIENT The function works for single output systems heating or cooling The self tuning action calculates optimum control parameter values during process startup The variable for ex...

Page 113: ...ing and exposed terminals on the back only for low power supply supply from Class 2 or low voltage limited energy source power supply lines must be separated from device input and output lines always...

Page 114: ......

Page 115: ...positive for output 1 terminals 21 22 ex Q13 Q14 Hy n 5 hysteresis negative for output 1 terminals 21 22 ex Q13 Q14 Keep pushing F until you see PASS release F and through the arrows set 99 push F and...

Page 116: ...t 99 push F and visualize Pro protection code from 128 through the arrows bring it back to 12 and keep F pushed until you come back to set point value Manual operation Keep pushed the lower left key f...

Page 117: ...tput 1 terminals 21 22 ex Q13 Q14 Keep pushing F until you see PASS release F and through the arrows set 99 push F and visualize Pro protection code default is 12 through the arrows set 128 and push F...

Page 118: ...push F and visualize Pro protection code from 128 through the arrows bring it back to 12 and keep F pushed until you come back to set point value Manual operation Keep pushed the lower left key for at...

Page 119: ...ar 6bar 6bar To modify it directly use up and down arrows By pushing F you go to parameter Transmitter 1 6bar 3bar 10bar 16bar 25bar 40bar Hy P 0 2bar 0 5bar 0 5bar 0 8bar 1 25bar 2bar Hy n 0bar 0bar...

Page 120: ...pushed F until visualization of Hrd Hrd CtrL 6 PID warm AL nr 1 but 1 diSP 0 Ld 1 1 Ld 2 28 Ld 3 20 Keep pushed F until you visualize PASS release F and through the arrows set 99 push F and visualize...

Page 121: ...lease F and through the arrows set 99 push F and visualize Pro protection code default is 12 through the arrows set 128 and push F keep it pushed until all parameters InF CFG InP Out PASS are visualiz...

Page 122: ...push F and visualize Pro protection code from 128 through the arrows bring it back to 12 and keep F pushed until you come back to set point value Manual operation Keep pushed the lower left key for at...

Page 123: ......

Page 124: ......

Page 125: ...WB1 QF A QF B...

Page 126: ......

Page 127: ......

Page 128: ...VERSIONE MD CON LCM100 TOGLIERE IL PONTE TRA I MORSETTI 6 7 E PARAMETRO BT3xx 0040 1 REGULATOR ON MD VERSION REMOVE THE BRIDGE BETWEEN TERMINALS 6 7 AND PARAMETER BT3xx 0040 1 REGULATOR ON...

Page 129: ......

Page 130: ......

Page 131: ...INTERFACE...

Page 132: ...R1 R2 POT...

Page 133: ...QF A QF B VERSIONE MD CON LCM100 TOGLIERE IL PONTE TRA I MORSETTI 6 7 E PARAMETRO BT3xx 0040 1 REGULATOR ON MD VERSION REMOVE THE BRIDGE BETWEEN TERMINALS 6 7 AND PARAMETER BT3xx 0040 1 REGULATOR ON...

Page 134: ...VERSIONE MD CON LCM100 TOGLIERE IL PONTE TRA I MORSETTI 6 7 E PARAMETRO BT3xx 0040 1 REGULATOR ON MD VERSION REMOVE THE BRIDGE BETWEEN TERMINALS 6 7 AND PARAMETER BT3xx 0040 1 REGULATOR ON...

Page 135: ......

Page 136: ......

Page 137: ......

Reviews: