Operation and Maintenance Manual - EN
10. Connection of the boiler D80P, P80 with a buffer tank and
controlled return water in to the boiler from control unit
ACD01 / ACD 03/04
INFO -
If using electronic regulation ACD01 / ACD 03/04, we do not connect any set or
other sensors in the boiler.
The sensors supplied as a part of the burner can be also used for ACD01 / ACD 03/04
regulation (TV = PF and TS = KSPF).
Regulation of the boiler’s exhaust fan (R) directly from the burner ATMOS A85.
Regulation of the functions of the pneumatic cleaning from the burner’s AC07X with
additional AC07X-C module – compressor (R5) and pneumatic el. valve (R6).
ACD01 / ACD 03/04 regulation controls the whole operation of both the boiler and the
heating system except exhaust fan of the boiler and pneumatic cleaning of the burner (direct controled
from the burner).
System configuration of parameters:
S6 = 3, S14 = 12, S15 = 1, S67 = 15, S68 = 16
M
Max. 60°C
M
WF
PF = TV
M1
DKP
VF1
AF
SF
VF2
M2
SLP
MKP2
obytné místnosti
haritable rooms
filtr
filter
vyrovnávací nádrž
buffer tank
1000 l
čerpadlo
pump
ventil
valve
bojler TUV
DHW boiler
tlakoměr, pojistný
ventil, odvzdušnovač
pressure gauge, safety
valve, deaerator
filtr
filter
ventil
valve
mísící ventil
mixing valve
čerpadlo
pump
tlaková
expansní
nádoba
pressure
expansion
vessel
mísící ventil
mixing valve
KSPF = TS
A85
A85
R5
R6
odtahový ventilátor
exhaust fan
SDW10/20
ARU5/10/30
ATMOS
ACD
R
Summary of Contents for A85
Page 1: ...Operation and Maintenance Manual EN www atmos cz Operation and Maintenance Manual ...
Page 2: ...www atmos cz Operation and Maintenance Manual EN ...
Page 61: ...Operation and Maintenance Manual EN EN www atmos cz EN 61 20 Expanded view of the burner ...
Page 66: ...EN www atmos cz 66 EN Operation and Maintenance Manual EN Notes ...