Operation and Maintenance Manual - EN
Setting up required output and combustion quality:
Required output is set up by parameters T4 and T6
The real output is, however, also affected by pellet diameter and an angle of the conveyor. That is why
it is necessary to know that when conveyor angle or pellet diameter were changed after set-up of the
burner, the burner must be set up again.
Quality of combustion is set up with the fan‘s air flap
in such way that the flame ends at the front
edge of the combustion chamber spherical space. This means that in boiler D80P, P80 flames fill the
entire space of the combustion chamber. However, reaching of the flames as far as the spherical space
of the boiler‘s body must be prevented.
Accurate final set-up of combustion is to be done after the boiler had been in continuous operation
for 30 to 60 minutes. The best way is to use an exhaust analyzer.
We recommend to set up the burner
so that
surplus O
2
in exhaust gas fluctuates between 7 to 10 % and average CO is less than 250 mg/
m
3
. Exhaust gas temperature must never drop below 110 °C and rise above 250 °C.
INFO - Although the burner has many functionalities (parameters), these only relate
to set up of the basic ones, which characterize output of the burner T4, T6 and quality
of combustion – fan‘s speed S3, air flap opening
Approximate recommended set up of the burner for separate outputs when using conveyors
DRA50 – 1.7, 2.5, 4 and 5 m, 6 mm pellets and the conveyor at an angle of 45°:
CAUTION - Parameter T4 must never be set higher than 9 s.
INFO
– If necessary, when there is little space in the boiler room, you may shorten the conveyor
(screw) or its legs as you wish at any time, but in such way that the conveyor angle remains
smaller than 45°.
Minimum length of the pipe between the burner and the conveyor must be more than
30 cm.
Maximum length of the pipe should not exceed 1 m.
• Parameter S1
–
Allowed number of attempts for ignition with fuel supply….
(2).
If parameter
S1 is set to 4, the fuel
will always be ignited
with both the ignition elements at
the same time (Z1 + Z2) in 2 attempts for
ignition with fuel supply.
CAUTION -
Always after the last attempt for ignition with fuel supply given by parameter
S1, an attempt for ignition without fuel supply will follow to test the equipment. If the fuel
is not ignited after this attempt, the system will be put out of operation and the
ALARM
START
error message will appear.
Boiler
output
Parameter
T1
Parameter
T4
Parameter
T6
Parameter
S3
Opening of the air
flap on the burner
fan of a boiler with
an exhaust fan
50 – 60 kW
85 s
5 s
12 s
30 %
47 mm
70 – 80 kW
85 s
8,3 s
12 s
47 %
67 mm
Summary of Contents for A85
Page 1: ...Operation and Maintenance Manual EN www atmos cz Operation and Maintenance Manual ...
Page 2: ...www atmos cz Operation and Maintenance Manual EN ...
Page 61: ...Operation and Maintenance Manual EN EN www atmos cz EN 61 20 Expanded view of the burner ...
Page 66: ...EN www atmos cz 66 EN Operation and Maintenance Manual EN Notes ...