Appendix
53
On Battery
Frequency
50/60Hz ± 3Hz
Outlets
- Total
8
9
Outlet Type
(8) IEC 320 C13
(8) IEC
320 C13 +
(1) IEC
320 C19
Outlets - Battery &
Surge Protected
8
9
Rated Power
Factor
>0.96
0.97
0.96
Crest Factor
3:1
Harmonic
Distortion
≦
2 % THDi (Linear Load)
≦
4 % THDi (Non-linear Load)
Voltage Regulation
± 1% (Batt)
Transfer Time (AC
to Batt.)
0ms
Transfer Time
(Inverter to Bypass)
4ms (ECO)
Battery
Runtime at Half
Load (min)
Half load
10.1
Half load
12.9
Half load
10.3
Half load
10.0
Half load
12.8
Half load
10.1
Runtime at Full
Load (min)
Full load
2.95
Full load
4.44
Full load
2.96
Full load
2.95
Full load
4.37
Full load
2.96
Battery Type
Sealed Lead-Acid
Battery Pack
Voltage
24V
36V
36V
48V
72V
72V
Battery Size
12V/9AH 12V/7AH 12V/9AH 12V/9AH 12V/7AH 12V/9AH
Battery Quantity
2
3
3
4
6
6
Hot-Swappable
Yes
Aten Model Name
OL1000
HV
OL1000
SHV
OL1500
HV
OL2000
HV
OL2000
SHV
OL3000
HV
Summary of Contents for OL1000HV
Page 3: ...UPS User Manual iii KCC Statement A RoHS This product is RoHS compliant...
Page 15: ...Chapter 1 Introduction 5 UPS HV Series Rear View...
Page 18: ...UPS User Manual 8 This Page Intentionally Left Blank...
Page 22: ...UPS User Manual 12...
Page 29: ...Chapter 2 Hardware Setup 19 3 Replace the front panel back to the unit...
Page 34: ...UPS User Manual 24 This Page Intentionally Left Blank...
Page 56: ...UPS User Manual 46 This Page Intentionally Left Blank...