UPS User Manual
34
Bypass Voltage Range Setting
Display: 07
Display: HS
Parameter 2: Acceptable high voltage
point and acceptable low voltage point
for Bypass mode.
Press the Up or Down
key to adjust the values.
HLS:
Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264:
setting the high voltage point from
230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140:
setting the high voltage point from
120Vac to 140Vac. (Default: 132Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220:
setting the low voltage point from
170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115:
setting the low voltage point from
85Vac to 115Vac. (Default: 85Vac)
Bypass Frequency Range Setting
Display: 08
Display: HS
Parameter 2: Acceptable high frequency
point and acceptable low frequency point
for Bypass mode.
Press the Up or Down
key to adjust the values.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss
point from 51Hz to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss
point from 61Hz to 65Hz(Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss
point from 45Hz to 49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss
point from 55Hz to 59Hz(Default: 57.0Hz)
Parameter 1 & Interface Display
Parameter 2 Description
Summary of Contents for OL1000HV
Page 3: ...UPS User Manual iii KCC Statement A RoHS This product is RoHS compliant...
Page 15: ...Chapter 1 Introduction 5 UPS HV Series Rear View...
Page 18: ...UPS User Manual 8 This Page Intentionally Left Blank...
Page 22: ...UPS User Manual 12...
Page 29: ...Chapter 2 Hardware Setup 19 3 Replace the front panel back to the unit...
Page 34: ...UPS User Manual 24 This Page Intentionally Left Blank...
Page 56: ...UPS User Manual 46 This Page Intentionally Left Blank...