Installation Instructions
SE LP10 9600 Series Exit Device
With MELR
Copyright © 2020, ASSA ABLOY Access and Egress Hardware Group, Inc. All
rights reserved. Reproduction in whole or in part without the express written
permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
6) Wiring Diagrams (Continued)
Alternate Indicator Configuration Application Diagram #2
Connect GREEN_LED input to switch controlled by panel. Shorting GREEN_LED to READER_NEG (Black) with
panel switch will override reader LED to keep it green.
12/24VDC System
12 Conductor
ElectroLynx Harness
From McKinney
Reader Electronics Requires 12VDC Filtered and Regulated
READER NEG - Black, 1
READER POS - Red, 2
DATA 1 - White, 3
DATA 0 - Green, 4
RX (NO) - Orange, 5
RX (COM) - Blue, 6
*EARTH GROUND - Brown, 7
**GREEN_LED - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
DPS (NC) - Pink, 11
DPS (COM) - Tan, 12
(-)
12VDC
(+)
DATA 1
DATA 0
RX (NO)
RX (COM)
Electrical
Access
Control
Panel
(By Others)
Use (NC) for
Fail Safe
Operation
Lock Relay
(NO) Fail
Secure
Operation
DPS
DPS
Power Supply
(By Others)
12-24VDC
H N G
- +
120 VAC
Input
Black (Hot)
White (Neutral)
Gr
een (Gnd)
QC12 Electric
Hinge From
McKinney
Panel Circuitry
*IMPORTANT: Pin 7 must be tied to earth ground in the access
control panel.
Wiring in accordance with the NEC, ANSI/NFPA 70
Fail secure installations are subject to approval of local AHJ
Fail secure installations shall permit use of Listed panic
hardware to allow emergancy exit from the protected area.
Failure to follow proper ESD safe grounding procedures could
lead to equipment failure.
(NO)
Panel Relay
(NC)
12VDC
- +
**UL294, S319, & BHMA A156.25 currently not applicable to Alternate Indicator option
12V
24V
Average
Peak
Average
Peak
Reader
100mA
220mA
n/a
n/a
Actuator (ET)
15mA
500mA
15mA
500mA