24
Installation Instructions
SE LP10 9600 Series Exit Device
With MELR
Copyright © 2020, ASSA ABLOY Access and Egress Hardware Group, Inc. All
rights reserved. Reproduction in whole or in part without the express written
permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
8) MELR Exit Device Configuration and Operational Check
Not Used
• Do not install the end cap until electrical operation is verified in order to confirm LED signaling.
• Do not discard the end cap and hardware.
Configuration Check
a. Locate controller at end of rail (Fig. 12A).
b. Ensure ‘Power Mode’ is set to ON as shown in Detail 12B.
NOTE:
For more information, refer to
FM434A MELR Exit Devices Installation & Wiring Instructions
.
>> Reference Section 5 - Wiring Diagrams for wiring device to EAC panel <<
Door Surface
DIP Switch Setting for
Power Mode Installation