10) Operational Check (Continued)
Feature
WT1
WT2
12 or 24VDC solenoid lock vol-
tage adjustable
X
X
Operates as Fail Safe or Fail
Secure
X
X
"Learn" mode allows testing of
specific cards without program-
ming at panel level
X
X
Card reader data integrity is vali-
dated at test unit
X
X
Displays detailed Wiegand data,
including hexadecimal string and
total bits received
X
Displays measured end-of-line
resistor values (if applicable)
X
The ASSA ABLOY Wiegand Test Unit verifies your installation in
the field*. The test unit checks for proper wiring, card reader data
integrity, lock functionality including lock/unlock, door position
status, and request-to-exit (REX) status.
In addition, this tool provides product demonstration abilities to
highlight the product’s features and capabilities.
Wiegand Test Unit
*For directions on use, see operating
instructions provided with unit.
Note:
Once electrical wiring has been successfully
completed according to proper application,
perform the following:
a. Turn power ON.
b. Verify LED located on reader is ON (Red or Green)
depending on reader configuration
c. Present valid credential and verify LED and
sounder activity.
d. Verify valid card read at EAC Panel.
e. Verify system operation functions; i.e., when valid credential
is presented to reader the door unlocks.
NOTE: Ensure LED operates as configured*:
• LED remains green when panel asserts GREEN_LED signal
*For configurations with GREEN_LED override enabled (Alternate Indicator Configuration);
see Application Diagram #2 in Section 6.