background image

507607-03

Issue 1827

Page 15 of 23

Seven-Segment Display Alert Codes

Code

Diagnostic Codes / Status of Equipment

Action Required to Clear and Recover

E105

Device communication problem - No other devices on RS 

BUS (Communication system).

Equipment is unable to communicate. Indicates numerous 

message errors. In most cases, errors are related to electrical 

noise. Make sure high voltage power is separated from 

RSBus. Check for mis-wired and/or loose connections 

between the stat, indoor unit, and outdoor unit. Check for a 

high voltage source of noise close to the system. Fault clears 

after communication is restored.

E120

Unresponsive device (Communicating systems only).

Usually caused by delay in outdoor unit responding to indoor 

unit poling. Recycle power. Check all wiring connections. 

Cleared after unresponsive device responds to any inquiry.

E124

Active communicating thermostat signal missing for more 

than 3 minutes (Communicating systems only).

Equipment lost communication with the thermostat. Check 

four wiring connections, ohm wires, and cycle power at the 

thermostat. Alert stops all services and waits for heartbeat 

message from thermostat (subnet controller). Cleared after 

valid thermostat (subnet) message is received.

E125

Control failed self-check, internal error, failed hardware. 

Will restart if error recovers, Integrated control not 

communicating Covers hardware errors (flame sense 

circuit faults, pin shorts, etc).

Hardware problem on the control. Cycle power on control. 

Replace if problem prevents service and is persistent. Cleared 

300 seconds after fault recovered.

E126

Control internal communication problem.

Hardware problem on the control. Cycle power on control. 

Replace if problem prevents service and is persistent. Cleared 

300 seconds after fault recovered.

E131

Corrupted control parameters (Verify configuration of 

system) (Communicating systems only).

Reconfigure the system. Replace control if heating or cooling 

is not available. Only applicable in the communicating mode 

not in startup. Exit from Commissioning and Execute Se+ 

factory Default mode. Control will still operate on default 

parameter settings.

E180

Outdoor air temperature sensor failure. Only shown if 

shorted or out of range (Communicating systems only)

Compare outdoor sensor resistance to temperature 

resistance charts in unit installation instructions. Replace 

sensor pack if necessary. At beginning of (any) configuration, 

furnace or air handler control will sense outdoor air and 

discharge air temperature sensor(s) If detected (reading 

in range), appropriate feature will be set as installed and 

that could be seen in 'About ' screen. In normal operation 

after control recognizes sensors, alarm will be sent if valid 

temperature reading is lost. To get rid of setting and alarm, 

redo configuration and make sure that temperature sensor is 

marked as not installed in indoor Unit ‘About’ screen. When 

indoor unit control is replaced thermostat will ‘tell’ new control 

if temperature sensor is in system or not. Clears 30 seconds 

after fault recovered.

E409

LSOM - Compressor low voltage.

Secondary voltages below 18VAC. After 10 minutes, operation 

is discontinued. Clears the code after voltage is higher than 

20VAC for 2 seconds or after power reset.

E410

The outdoor unit pressure is below the required limit.

Unit pressure is below the lower limit. The system is shut 

down. The low pressure switch for HFC410A will open at 

40 PSIG and close at 90 PSIG. Confirm that the system is 

properly charged with refrigerant. Check TXV, indoor unit 

blower motor, dirty filters or clogged refrigerant filter. Confirm 

that the evaporator coil is clean. The alarm clears after the 

pressure switch closes or after a power rest.

NOTE

Additional codes may be found in the Comfort Sync room thermostat manual.

Table 5. 7-Segment Alert and System Status Codes

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: