Mode

Description

Example of Display

Anti-Short Cycle 

Delay

Middle line shall blink at 1 Hz for 2 seconds, followed by a two-second 

display of the rounded up number of minutes left in the timer (two 

minutes, one second shall be displayed as “3”). The Anti-Short Cycle 

Delay time remaining is displayed when the delay is active.

Cooling Stage

Shows what stage of heat pump is 

currently operating.

Following string is repeated if two-stage cooling is active with outdoor 

fan speed set at 700 RPM. 

NOTE

: A - If available, displays outdoor 

ambient temperature.

C2

 pause 

F700

 pause

Heat Pump Stage

Shows what stage of heat pump is 

currently operating.

Following string is repeated if first-stage cooling is active with outdoor 

fan speed set at 600 RPM. 

NOTE

: A - If available, displays outdoor 

ambient temperature.

H1

 pause 

F600

 pause

Defrost Mode

Shown only while in an active defrost.

Following string is repeated if defrost is active while unit was in first-

stage heat pump heating mode:

dF

 pause 

H1

 pause

Dehumidification 

Mode

Shows that the unit is providing 

dehumidification  instead  of  straight 

cooling.

Following string is repeated if dehumidification is active with outdoor 

fan speed set at 225 RPM:

d

 pause 

f225

 pause

Diagnostic Recall

Shows the last 10 stored diagnostic 

error codes.

If first error is 

E250

, second 

E231:E

 pause 

250

 pause 

E

 pause 

231

Next codes (up to 10) are shown using same method.

If there are no error codes stored: 

E

 pause 

000

Fault Memory 

Clear

After the fault memory is cleared, the following string is displayed with 

0.5 seconds character on/off time:

0000

 pause

Active error in 

outdoor control 

idle mode

Shows all active error(s) codes.

Following string is repeated if Error E125 and E201 are present:

E125

 pause 

E201

Active error in run 

mode

Shows current status and all active 

error(s) codes.

Following string is repeated if Error E311 is present while blower speed 

at 700 RPM:

F700

 pause 

E311

Outdoor Ambient 

Temperature 

(OAT)

Any time OAT is sensed in operating 

range, value is displayed if unit is in 

diagnostic and non-diagnostic modes.

Following string is repeated if second stage cooling is active with 

outdoor fan speed set at 650 RPM and OAT is 104°F:

C2

 pause 

F650

 pause 

A104

 pause

Outdoor Coil 

Temperature 

(OCT)

Any time OCT is sensed in operating 

range, value is displayed if unit is in 

diagnostic mode.

Following string is repeated if 2nd stage heat is active with outdoor fan 

speed set at 550 RPM and OCT is 25°F:

H2

 pause 

F550

 pause 

c25

 pause

Discharge Line 

Temperature (DIS)

Any time DIS is sensed in operating 

range, value is displayed if unit is in 

diagnostic mode.

Following string is repeated if 2nd stage cooling is active with outdoor 

fan speed set at 650 RPM and DIS is 185°F

C2

 pause 

F650

 pause 

d185

 pause

*Information will be displayed, but does not apply to this unit.

Table 6. Outdoor Control 7-Segment Unit Status Displays

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: