background image

507607-03

Issue 1827

Page 16 of 23

Code

Diagnostic Codes / Status of Equipment

Action Required to Clear and Recover

E411

The low pressure switch has opened 5 times during one 

cooling cycle. As a result, the system will shut down.

Open low pressure switch error count reached 5 strikes. The 

low pressure switch for R410A will open at 40 PSIG and close 

at 90 PSIG. Confirm that the system is properly charged with 

refrigerant. Check TXV, indoor unit blower motor, dirty filters 

or clogged refrigerant filter. Confirm that the evaporator coil is 

clean. The alarm clears after a power rest.

E412

The outdoor unit pressure is above the required limit. The 

system will shut down.

Unit pressure is above the upper limit. System is shut down. 

The high pressure switch for HFC410A will open at 590 PSIG 

and close at 418 PSIG. Confirm that the system is properly 

charged with refrigerant. Check condenser fan motor, TXV, 

indoor unit blower motor, stuck reversing valve or clogged 

refrigerant filter. Confirm that the outdoor unit is clean. The 

alarm clears after 4 consecutive normal compressor run 

cycles, the pressure switch closes or a power reset.

E413

The high pressure switch has opened 5 times during one 

cooling cycle. As a result, the Comfort Sync thermostat 

will shut down.

Open high pressure switch error count reached 5 strikes. 

System is shut down. The high pressure switch for HFC410A 

will open at 590 PSIG and close at 418 PSIG. Confirm that the 

system is properly charged with refrigerant. Check condenser 

fan motor, TXV, indoor unit blower motor, stuck reversing 

valve or clogged refrigerant filter. Confirm that the outdoor unit 

is clean. The alarm clears after a power reset.

E414

The discharge line temperature is higher than the 

recommended upper limit of 279°F.

Discharge line temperature is > 279°F. Confirm that the 

system is properly charged with refrigerant. Check system 

operating pressures and compare to unit charging charts in 

installation manual. Confirm that the outdoor unit is clean. The 

alarm clears after the discharge temperature is < 225°F.

E415

The discharge line temperature has been consistently 

higher than the recommended upper limit of 279°F.

Discharge line high temperature error count reached 5 

strikes. Confirm that the system is properly charged with 

refrigerant. Check system operating pressures and compare 

to unit charging charts in installation manual. Confirm that the 

outdoor unit is clean. The alarm clears after the discharge 

temperature is < 225°F. The alarm clears after a power reset.

E416

The outdoor coil sensor is either open, short-circuited 

or the temperature is out of sensor range. As a result, 

the outdoor unit control will not perform any defrost 

tempering.

Coil sensor being detected open or shorted, or temperature is 

out of coil sensor range. Outdoor unit control will not perform 

demand or time/temperature defrost operation. System will 

still heat or cool. Check the resistance of the coil sensor and 

compare to temperature resistance chart. Replace coil sensor 

if needed. The alarm clears when outdoor unit control detects 

proper coil sensor readings or after a power reset.

E417

The outdoor unit discharge sensor is either open, short-

circuited or the temperature is out of sensor range. As a 

result, the outdoor unit control will not perform any defrost 

tempering.

Outdoor unit control detects open or shorted discharge 

sensor, or temperature that is out of discharge sensor range. 

Check the resistance of the discharge sensor and compare 

to temperature resistance chart; replace if needed. Reset 

by replacing the discharge sensor. This fault is detected 

by allowing the unit to run for 90 seconds before checking 

discharge sensor resistance. If the discharge sensor 

resistance is not within range after 90 seconds, the board will 

count one fault. After 5 faults, the board will lock out. Check 

for proper sensor reading and attachment to line. The alarm 

clears after a power reset.

E418

There is a faulty W output circuit.

Faulty W output circuit. Confirm that the unit is not running. 

Check for mis-wiring. Disconnect thermostat lines from W 

and verify 24VAC on the W. If 24VAC is present, replace the 

board.

E419

The W output on the outdoor unit has reported more 

than 5 errors. As a result, the system has shut down the 

outdoor unit.

W output hardware fault count reached 5 strikes.

NOTE

Additional codes may be found in the Comfort Sync room thermostat manual.

Table 5. 7-Segment Alert and System Status Codes

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: