background image

507607-03

Issue 1827

Page 14 of 23

Seven-Segment Alert and System Status 

Codes

Alert codes are displayed using the seven segment display 

located on the outdoor control.

NOTE: 

System fault and lockout alarm code displays takes 

precedence over system status (cooling, heating stages or 

defrost/dehumidification).

The seven segment will display an abnormal condition 

(error code) when detected in the system. A list of the 

codes are shown in Table 5.

Re-Setting Alert Codes

Alert codes can be reset manually or automatically:

Manual Reset

Manual reset can be achieved by one of the following 

methods:

•  Disconnecting R wire from the main control’s R 

terminal.

•  Turning the indoor unit off and back on again. After 

power up all existing codes will display 60 seconds 

and then clear.

Automatic Reset

After an alert is detected, the main control continues to 

monitor the unit’s system and compressor operations. 

When/if conditions return to normal, the alert code is turned 

off automatically.

Operation

Outdoor unit and indoor blower cycle on demand from 

the room thermostat. When the thermostat blower switch 

is moved to the ON position, the indoor blower operates 

continuously.

Filter Drier

The  unit  is  equipped  with  a  large  capacity  bi-flow  filter 

which keeps the system clean and dry. If replacement is 

necessary, replace with one of similar design and capacity. 

The replacement filter drier must be suitable for use with 

R410A refrigerant.

Crankcase Heater

If unit is equipped with a crankcase heater, it should 

be energized 24 hours before unit start-up to prevent 

compressor damage as a result of slugging.

Emergency Heat Function (Room Thermostat)

An emergency heat function is designed into some room 

thermostats. This feature is applicable when isolation of 

outdoor unit is required or when auxiliary electric heat is 

staged by outdoor thermostats. When the room thermostat 

is placed in the emergency heat position, the outdoor unit 

control circuit is isolated from power and the field-supplied 

relays bypass the outdoor thermostats. An amber indicating 

light simultaneously comes on to remind the homeowner 

that the unit is operating in the emergency heat mode.

Emergency heat is usually used during an outdoor 

shutdown, but it should also be used following a power 

outage if power has been off for over an hour and the 

outdoor temperature is below 50°F. System should be left 

in the emergency heat mode at least 6 hours to allow the 

crankcase  heater  sufficient  time  to  prevent  compressor 

slugging.

Outdoor unit and indoor blower cycle on demand from 

the room thermostat. When the thermostat blower switch 

is moved to the ON position, the indoor blower operates 

continuously.

Time Delay

The timed-off delay is 5 minutes long. The delay helps 

to protect the compressor from short cycling in case the 

power to the unit is interrupted or a pressure switch opens. 

Pressure Switch Circuit

The control includes two pressure switch circuits. A high 

pressure switch is connected to the board’s HI-PS terminals 

(Figure 14). The low pressure, or loss-of-charge pressure 

switch, is connected to the LO-PS terminals.

During a single demand cycle, the defrost control will lock 

out the unit after the fifth time that the circuit is interrupted 

by and pressure switch wired to the control board. In 

addition, the diagnostic LEDs will indicate a locked-out 

pressure  switch  after  the  fifth  occurrence  of  an  open 

pressure switch.

The unit will remain locked out until power to the board 

is interrupted, then re-established, or until the error is 

cleaned.

NOTE: 

The  control  board  ignores  input  from  the  low 

pressure switch terminals as follows:

•  During the TEST mode
•  During the 90 seconds start-up period

Fan Cycling (J3)

Fan cycling routine when activated will cycle the fan ON 

(Figure  14)  for  five  minutes  if  the  outdoor  ambient  air 

temperature is between 15ºF and 35ºF and the compressor 

has been OFF for 25 to 30 minutes. This option is to help 

reduce  the  potential  for  ice  build  up  on  the  orifice  ring 

during system OFF cycles that are greater than 25 to 30 

minutes.

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: