background image

507607-03

Issue 1827

Page 9 of 23

Figure 11. 

An R410A system will not operate properly with an R-22 

metering device.

Install the refrigerant metering device as shown in Figure 

11. Do not twist cap tubes when loosening the seal nut from 

the orifice housing. Use wrench to back up the distributor.

Expansion Valve Systems

Expansion valves equipped with Chatleff-type fittings are 

available from the manufacturer. See Table 3 for proper 

TXV for each unit.

Model

Part Number

4SCU16LS-24-36

A4TXV01

4SCU16LS-48

A4TXV02

4SCU16LS-60

A4TXV02

Table 3. TXV Data

To install an expansion valve (Figure 11):

1.  Separate the distributor assembly and remove the 

piston orifice and used Teflon seal. Insert nozzle end 

of the expansion valve along with a new Teflon seal 

into the distributor and tighten to 20 - 30 ft. lbs. Use 

backup wrench on all wrench flats. Overtightening will 

crush the Teflon seal and may cause a leak.

2.  Attach liquid line portion of distributor assembly along 

with new Teflon seal to the inlet of the expansion valve. 

Tighten to 20 - 30 ft. lbs. Use backup wrench on all 

wrench flats. Overtightening will crush the Teflon seal 

and may cause a leak.

3.  Connect the external equalizer line to the equalizer 

port on the suction line and tighten to 8 ft. lbs.

4.  Strap the superheat sensing bulb to the suction header.

If installing an expansion valve on an indoor coil that 

previously  used  a  fixed  orifice,  be  sure  to  remove  the 

existing fixed orifice. Failure to remove a fixed orifice when 

installing an expansion valve to the indoor coil will result in 

improper operation and damage to the system.

Manifold Gauge Set

Manifold gauge sets used with systems charged with 

R410A refrigerant must be capable of handling the higher 

system operating pressures. The gauges should be rated 

for use with pressures 1 - 800 on the high side and a low 

side of 30” vacuum to 250 psi with dampened speed to 500 

psi. Gauge hoses must be rated for use at up to 800 psi of 

pressure with a 4000 psi burst rating.

Liquid and Suction Line Service Valves

The liquid line and suction line service valves (Figure 12) 

and service ports are used for leak testing, evacuation, 

charging, and checking charge.

Each valve is equipped with a service port which has a 

factory-installed Schrader valve. A service port cap protects 

the Schrader valve from contamination and serves as the 

primary leak seal.

To Access the Schrader Port:

1.  Remove the service port cap with an adjustable 

wrench.

2.  Connect gauge to the service port.
3.  When testing is completed, replace service port cap. 

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

1.  Remove stem cap with an adjustable wrench.

2.  Use service wrench with a hex-head extension to back 

the stem out counterclockwise as far as it will go. Use a 

3/16” hex head extension for liquid line service valves 

and a 5/16” extension for suction line service valves.

3. 

Replace the stem cap. Tighten finger tight, then tighten 

an additional 1/6 turn.

To Close Liquid or Suction Line Service Valve:

1.  Remove the stem cap with an adjustable wrench.

2.  Use a service wrench with a hex-head extension to 

turn the stem clockwise to seat the valve. Tighten 

firmly.

3.  An R410A system will not operate properly with an 

R-22 metering device.

Suction Line (Ball Type) Service Valve

Suction line (ball type) service valves function the same 

way as the other valves; the difference is in the construction 

(Figure 13).

The ball valve is equipped with a service port with a factory-

installed Schrader valve. A service port cap protects the 

Schrader valve from contamination and serves as the 

primary seal.

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: