background image

507607-03

Issue 1827

Page 2 of 23

Installation

General

Read this entire instruction manual, as well as the 

instructions supplied in separate equipment, before 

starting the installation. Observe and follow all warnings, 

cautions, instructional labels, and tags. Failure to comply 

with these instructions could result in an unsafe condition 

and/or premature component failure.

These instructions are intended as a general guide only 

for use by qualified personnel and do not supersede any 

national or local codes in any way. The installation must 

comply with all provincial, state, and local codes as well as 

the National Electrical Code (U.S.) or Canadian Electrical 

Code (Canada). Compliance should be determined prior 

to installation.

4SCU16/18LS condensing units use R410A which is an 

ozone-friendly HFC refrigerant. The unit must be installed 

with  a  matching  indoor  coil  and  line  set.  A  filter  drier 

approved for use with R410A is installed in the unit.

NOTE: 

This product has been designed and manufactured 

to meet ENERGY STAR criteria for energy efficiency when 

matched  with  appropriate  coil  components.  However, 

proper  refrigerant  charge  and  proper  air  flow  are  critical 

to  achieve  rated  capacity  and  efficiency.  Installation  of 

this  product  should  follow  the  manufacturer’s  refrigerant 

charging and air flow instructions. Failure to confirm proper 

charge  and  airflow  may  reduce  energy  efficiency  and 

shorten equipment life.

When servicing or repairing HVAC components, ensure 

the fasteners are appropriately tightened. Table 1 shows 

torque values for fasteners.

Table 1. Torque Table

Fastener 

Torque

Stem Caps

8 ft. lbs.

Service Port Caps

8 ft. lbs.

Sheet Metal Screws 

16 in. lbs.

#8 Machine Screws 

16 in. lbs.

#10 Machine Screws

28 in. lbs.

Compressor Bolts 

90 in. lbs.

Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possible 

shipping damage. If damage is found, it should be noted 

on the carrier’s freight bill. Take special care to examine 

the unit inside the carton if the carton is damaged. Any 

concealed damage discovered should be reported to the 

last carrier immediately, preferably in writing, and should 

include a request for inspection by the carrier’s agent. If 

any damages are discovered and reported to the carrier 

DO NOT INSTALL THE UNIT

, as claim may be denied.

Check the unit rating plate to confirm specifications are as 

ordered.

Location of Unit

Outdoor units operate under a wide range of weather 

conditions; therefore, multiple factors must be considered 

when positioning the unit. The unit must be positioned 

to  give  adequate  clearances  for  sufficient  airflow  and 

servicing. Refer to Figure 1 for installation clearances.

•  Place a sound-absorbing material, such as Isomode 

under the unit if it will be installed in a location or 

position that will transmit sound or vibration to the 

living area or adjacent buildings.

Figure 1. Installation Clearances

* A service clearance of 30” must be maintained on one of the 

sides adjacent to the control box. Clearance to one of the other 

three sides must be 36”. Clearance to one of the remaining two 

sides may be 12” and the final side may be 6”.

A clearance of 24” must be maintained between units.

48” clearance required on top of unit. Maximum soffit overhang is 

36”.

Slab Mounting

When installing a unit at grade level, install on slab high 

enough above grade so that water from higher ground will 

not collect around the unit (Figure 2).

Figure 2. Slab Mounting

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: