background image

507607-03

Issue 1827

Page 8 of 23

Flushing Existing Line Set and Indoor Coil

This procedure should not be performed on systems which 

contain contaminants, such as compressor burn out.

Required Equipment

The following equipment is needed to flush the existing line 

set and indoor coil (Figure 10). Two clean R-22 recovery 

bottles, an oil-less recovery machine with a “pump down” 

feature, and two sets of gauges (one for use with R-22 and 

one for use with R-410A).

Flushing Procedure

NOTE: 

The line set and/or indoor coil must be flushed with 

at  least  the  same  amount  of  refrigerant  that  previously 

charged  the  system.  Check  the  charge  in  the  flushing 

cylinder before flushing the unit.

1.  Remove existing R-22 refrigerant using the appropriate 

procedure.

If the existing outdoor unit is not equipped with shutoff 

valves, or if the unit is not operational AND the existing 

R-22 refrigerant will be used to flush the system:

Disconnect all power to the existing outdoor unit. Connect 

the existing unit, a clean recovery cylinder, and the 

recovery machine according to the instructions provided 

with the recovery machine. Remove all R-22 refrigerant 

from the existing system. Refer to the gauges after 

shutdown to confirm that the entire system is completely 

void of refrigerant. Disconnect the liquid and suction lines 

from the existing outdoor unit.

If the existing outdoor unit is equipped with manual shutoff 

valves AND new R-22 refrigerant will be used to flush the 

system:

Start the existing R-22 refrigerant system in cooling mode 

and close the liquid line valve. Pump all the existing R-22 

refrigerant back into the outdoor unit.

(It may be necessary to bypass the low pressure switches 

to ensure complete refrigerant evacuation.)

When the low side system pressures reach 0 psig, close 

the suction line valve. Disconnect all power to the existing 

outdoor unit. Refer to the gauges after shutdown to confirm 

that  the  valves  are  not  allowing  refrigerant  to  flow  back 

into the low side of the system. Disconnect the liquid and 

suction lines from the existing outdoor unit.

2.  Remove the existing outdoor unit. Set the new R-410A 

unit and follow the brazing connection procedure 

outlined previously to make line set connections. Do 

not install the R-410A thermal expansion valve at this 

time.

3.  Make low voltage and line voltage connections to the 

new outdoor unit. Do not turn on power to the unit or 

open the outdoor unit service valves at this time.

4. 

Remove  the  existing  R-22  refrigerant  flow  control 

orifice  or  thermal  expansion  valve  before  continuing 

with  flushing  procedures.  R-22  flow  control  devices 

are not approved for use with R-410A refrigerant and 

may  prevent  proper  flushing.  Use  a  field-provided 

fitting to reconnect the lines.

5.  Remove the pressure tap valve cores from the 

4SCU16/18LS units service valves. Connect an R-22 

cylinder with clean refrigerant to the suction service 

valve. Connect the R-22 gauge set to the liquid line 

valve and connect a recovery machine with an empty 

recovery tank to the gauge set.

6.  Set the recovery machine for liquid recovery and start 

the recovery machine. Open the gauge set valves to 

allow the recovery machine to pull a vacuum on the 

existing system line set and indoor coil.

7.  Invert the cylinder of clean R-22 and open its valve to 

allow liquid refrigerant to flow in to the system through 

the suction line valve. Allow the refrigerant to pass from 

the cylinder and through the line set and the indoor coil 

before it enters the recovery machine.

8.  After all of the liquid refrigerant has been recovered, 

switch the recovery machine to vapor recovery so that 

all of the R-22 vapor is recovered. Allow the recovery 

machine to pull a vacuum on the system.

NOTE: 

A  single  system  flush  should  remove  all  of 

the mineral oil from the existing refrigerant lines and 

indoor  coil.  A  second  flushing  may  be  done  (using 

clean refrigerant) if insufficient amounts of mineral oil 

were removed during the first flush. After each system 

flush, allow the recovery machine to pull a vacuum on 

the system at the end of the procedure.

9.  Close the valve on the inverted R-22 cylinder and the 

gauge set valves. Pump the remaining refrigerant out 

of the recovery machine and turn the machine off.

10.  Use nitrogen to break the vacuum on the refrigerant 

lines and indoor coil before removing the recovery 

machine, gauges, and R-22 refrigerant drum. Re-

install pressure tap valve cores into the 4SCU16/18LS 

unit’s service valves.

11. 

Install  the  fixed  orifice  (or  thermal  expansion  valve 

approved for use with R-410A refrigerant) in the liquid 

line at the indoor coil.

Refrigerant Metering Device

4SCU16/18LS units are designed for use with TXV 

systems. Refer to the appropriate following section for 

information on installing the chosen refrigerant metering 

device.

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: